Honeywell
• 41
C
OMMISSIONING
5.1
Commissioning of the SmartVFD HVAC
1
Read carefully the safety instructions in Chapter 1 and above and follow them.
2
After the installation, make sure that:
•
both the drive and the motor are grounded.
•
the mains and motor cables comply with the requirements given in chapter
4.1.1.
•
the control cables are located as far as possible from the power cables,
see chapter 4.4.
•
the shields of the shielded cables are connected to protective ground
marked with
.
•
check the tightening torques of all terminals
•
the wires do not touch the electrical components of the drive.
•
the common inputs of digital input groups are connected to +24V or
ground of the I/O terminal or the external supply.
3
Check the quality and quantity of cooling air (chapter 3.2 and Table 6).
4
Check the inside of the drive for condensation.
5
Check that all Start/Stop switches connected to the I/O terminals are in
Stop-position.
6
Before connecting the AC drive to mains:
•
check mounting and condition of all fuses and other protective devices
7
Run the Startup Wizard (see the Application Manual).