Honeywell
• 23
HVAC A
PPLICATION
3.3
HVAC Application - Quick setup parameter group
The Quick Setup parameter group is a collection of parameters that are most commonly used
during installation and commissioning. They are collected in the first parameter group so that
they can be found fast and easily. They can, however, be also reached and edited in their ac-
tual parameter groups. Changing a parameter value in the Quick setup group also changes the
value of this parameter in its actual group.
Code
Parameter
Min
Max
Unit
Default
ID
Description
M1.1
Motor nominal voltage
Varies
Varies
V
Varies
110
Find this value U
n
on the
rating plate of the motor.
See page 33.
M1.2
Motor nominal fre-
quency
8.00
320.00
Hz
60.00
111
Find this value f
n
on the rat-
ing plate of the motor. See
page 33.
M1.3
Motor nominal speed
24
19200
rpm
1720
112
Find this value n
n
on the rat-
ing plate of the motor.
M1.4
Motor nominal current
Varies
Varies
A
Varies
113
Find this value I
n
on the rat-
ing plate of the motor.
M1.5
Motor Cos Phi
0.30
1.00
0.80
120
Find this value on the rating
plate of the motor
M1.6
Motor nominal power
0.00
Varies
kW
Varies
116
Find this value I
n
on the rat-
ing plate of the motor.
M1.7
Motor current limit
Varies
Varies
A
Varies
107
Maximum motor current
from AC drive
M1.8
Minimum frequency
0.00
M3.3.1
Hz
Varies
101
Minimum allowed frequency
reference
M1.9
Maximum frequency
M3.3.1
320.00
Hz
60.00
102
Maximum allowed frequency
reference
M1.10
I/O control reference A
selection
1
8
7
117
Selection of ref source when
control place is I/O A. See
page 36 for selections.
M1.11
Preset frequency 1
M3.3.1
300.00
Hz
10.00
105
Select with digital input:
Preset frequency selection 0
(M3.5.1.16)
M1.12
Preset frequency 2
M3.3.1
300.00
Hz
15.00
106
Select with digital input:
Preset frequency selection 1
(M3.5.1.17)
M1.13
Acceleration time 1
0.1
3000.0
s
20.0
103
Time to accelerate from zero
to maximum frequency
M1.14
Deceleration time 1
0.1
3000.0
s
20.0
104
Time to decelerate from min-
imum to zero frequency
M1.15
Remote control place
1
2
1
172
Selection of remote control
place (start/stop)
1 = I/O
2 = Fieldbus
M1.16
Automatic reset
0
1
0
731
0 = Disabled
1 = Enabled
M1.17
PID Mini-Wizard
0
1
0
1803
0 = Inactive
1 = Activate
See chapter 1.2.
Summary of Contents for SmartVFD HVAC MR4
Page 7: ...Honeywell 5 SAFETY ...
Page 49: ...Honeywell 47 COMMISSIONING ...
Page 78: ...STARTUP Honeywell 6 ...