PID Mini-Wizard
The PID mini wizard is activated in the Quick Setup menu. This wizard presupposes that you
are going to use the PID controller in the "one feedback / one setpoint" mode. The control place
will be I/O A and the default process unit ‘%’.
The
PID mini wizard
asks for the following values to be set:
If any other process unit than ‘%’ is selected the following questions appear: If not the Wizard
will directly jump to step 5
.
If one of the analogue input signals is selected the question 6 appears. Otherwise you will be
taken to question 7.
If one of the analogue input signals is selected the question 9 appears. Otherwise you will be
taken to question
11.
If either of the options Keypad Setpoint 1 or 2 is chosen the question 10
will appear.
If option ‘Yes’ is selected you will be prompted for three more values:
1
Process unit selection
(Several selections. See par.
M3.12.1.4)
2
Process unit min
3
Process unit max
4
Process unit decimals
0...4
5
Feedback 1 source selection
See page 57 for selections.
6
Analogue input signal range
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See page 42.
7
Error inversion
0 = Normal
1 = Inverted
8
Setpoint source selection
See page 55 for selections.
9
Analogue input signal range
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See page 42.
10
Keypad setpoint
11
Sleep function?
No
Yes
12
Sleep frequency limit 1
0.00...320.00 Hz
13
Sleep delay 1
0...3000 s