HVAC A
PPLICATION
Honeywell
• 48
3.5.9
Group 3.7: Prohibit Frequencies
In some systems it may be necessary to avoid certain frequencies due to mechanical reso-
nance problems. By setting up prohibit frequencies it is possible to skip these ranges.
Table 34. Prohibit frequencies
Code
Parameter
Min
Max
Unit
Default
ID
Description
M3.7.1
Prohibit frequency
range 1 low limit
-1,00
320,00
Hz
0,00
509 0 = Not used
M3.7.2
Prohibit frequency
range 1 high limit
0,00
320,00
Hz
0,00
510 0 = Not used
M3.7.3
Prohibit frequency
range 2 low limit
0,00
320,00
Hz
0,00
511
0 = Not used
M3.7.4
Prohibit frequency
range 2 high limit
0,00
320,00
Hz
0,00
512 0 = Not used
M3.7.5
Prohibit frequency
range 3 low limit
0,00
320,00
Hz
0,00
513 0 = Not used
M3.7.6
Prohibit frequency
range 3 high limit
0,00
320,00
Hz
0,00
514 0 = Not used
M3.7.7
Ramp time factor
0,1
10,0
Times
1,0
518
Multiplier of the currently
selected ramp time between
prohibit frequency limits.
M3.7.8
Resonance sweep
acc/dec time
0.1
3000.0
s
20.0
1812
Acceleration and decelera-
tion times to be used during
resonance sweep.