Honeywell
• 37
HVAC A
PPLICATION
Table 25. Control reference settings
M3.3.10
Preset frequency
mode
0
1
0
182
0 = Binary coded
1 = Number of inputs. Preset
frequency is selected accord-
ing to how many of preset
speed digital inputs are
active
M3.3.11
Preset frequency 0
M3.3.1
M3.3.2
Hz
5.00
180
Basic preset frequency 0
when selected by Control ref-
erence parameter (M3.3.3).
M3.3.12
Preset frequency 1
M3.3.1
M3.3.2
Hz
10.00
105
Select with digital input:
Preset frequency selection 0
(M3.5.1.16)
M3.3.13
Preset frequency 2
M3.3.1
M3.3.2
Hz
15.00
106
Select with digital input:
Preset frequency selection 1
(M3.5.1.17)
M3.3.14
Preset frequency 3
M3.3.1
M3.3.2
Hz
20.00
126
Select with digital inputs:
Preset frequency selection 0
& 1
M3.3.15
Preset frequency 4
M3.3.1
M3.3.2
Hz
25.00
127
Select with digital input:
Preset frequency selection 2
(M3.5.1.18)
M3.3.16
Preset frequency 5
M3.3.1
M3.3.2
Hz
30.00
128
Select with digital inputs:
Preset frequency selection 0
& 2
M3.3.17
Preset frequency 6
M3.3.1
M3.3.2
Hz
40.00
129
Select with digital inputs:
Preset frequency selection 1
& 2
M3.3.18
Preset frequency 7
M3.3.1
M3.3.2
Hz
50.00
130
Select with digital inputs:
Preset frequency selection 0
& 1 & 2
M3.3.19
Preset alarm fre-
quency
M3.3.1
M3.3.2
Hz
25.00
183
This frequency used when
fault response (in Group 3.9:
Protections) is Alarm+preset
frequency
M3.3.20
Motor potentiometer
ramp time
0.1
500.0
Hz/s
10.0
331
Rate of change in the motor
potentiometer reference
when increased or
decreased.
M3.3.21
Motor potentiometer
reset
0
2
1
367
Motor potentiometer fre-
quency reference reset logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down