S7999B SYSTEM DISPLAY
75
65-0283—2
Setpoints:
None
APPLICATION NOTE
Application:
Feed Pump
Description:
Monitor digital inputs to start and stop boiler feedwater and to alarm an open circuit on
high water condition.
Digital Inputs:
None
Digital Outputs:
Start-Stop relay (ON when Start boiler in
ON, OFF otherwise)
High Water Alarm (ON when high water
alarm input is ON, OFF when high water
alarm input is OFF)
Analog Inputs:
Level Transmitter
(4-20 mA)
Analog Outputs:
None
Application File:
pump01.nge
Range
0–100%
Controller
Model
DC2500-EB-200R-200-00000-00-0
Algorithm:
CTRALG
ONOFF
TIMER
DIS
Output:
OUTALG
RLY
Input 1:
IN1TYP
4–20
IN1 HI
100
IN1 LO
0
Input 2:
IN2TYP
DIS
Control:
LSP’S
1 ONLY
SP TRK
NONE
PWR UP
ALSP
SP Hi
100
SP Lo
0
ACTION
REV
HYST
0
Options:
AUXOUT
DIS
DIGIN1
NONE
DIGIN2
NONE
Communications:
ComADR
40
ComSTA
MODB
BAUD
19.2K
TX_DLY
1
WS FLT
FP B
SDENAB
DIS