S7999B SYSTEM DISPLAY
69
65-0283—2
Setpoints:
High or Low temperature alarm (0-500°F)
FGR Permissive (0-500°F)
APPLICATION NOTE
Application:
Stack Temperature
Description:
Monitor stack temperature and alarm when temperature is too high. Optionally output an
FGR permissive signal when stack temperature reaches permitted level.
M24239
FLUE GAS
PERMISSIVE
CIRCUITRY
MODBUS COMMUNICATION
HONEYWELL S7810M
L1
ALARM (HIGH
STACK TEMP)
L1
D+
+
-
R
D-
SHIELD
J THERMOCOUPLE
26
27
25
17 18
16
6
4
5
9
8
7
L2
L1
G
C
A
B
L1
L2
UDC
CONTROLLER
Digital Inputs:
None
Digital Outputs:
High Temperature Alarm (ON
when at or above alarm
setpoint, OFF when below
alarm setpoint).
Analog Inputs:
Stack temperature sensor (0-
500°F)
Analog Outputs:
None
Application File:
stack01.nge
stack02.nge
Description
0-500°F High Stack Temperature
0-500°F High Stack Temperature
FGR Permissive
Controller Model
UDC2500
DC2500-EB-200R-100-00000-00-0
UDC2500
DC2500-EB-200R-100-00000-00-0
Algorithm:
CTRALG
ONOF (ON/OFF)
ONOF (ON/OFF)
TIMER
DIS
DIS
Output:
OUTALG
RLY (Time Simplex)
RLY (Time Simplex)
Input 1:
IN1TYP
J L
J L
IN1 HI
550
550
IN1 LO
20
20
Input 2:
IN2TYP
DIS (Disable)
DIS (Disable)
Control:
LSP’S
ONE
ONE
SP TRK
NONE
NONE
PWR UP
ALSP
ALSP
SP Hi
500
500
SP Lo
20
20
ACTION
REV
REV