S7999B SYSTEM DISPLAY
65-0283—2
68
1 DC2500-CE-200R-200-00000-00-0
2 DC3200-CE-200R-210-10000-00-0
3
Low Fire Hold alarm uses setpoint 1 of alarm 2. If this alarm setpoint is disabled (A2S1TY is NONE), then this alarm is disabled.
Control:
LSP’S
1 ONLY
1 ONLY
1 ONLY
1 ONLY
SP TRK
NONE
NONE
NONE
NONE
PWR UP
ALSP
ALSP
ALSP
ALSP
SP Hi
300
300
500
500
SP Lo
0
0
0
0
ACTION
REV
REV
REV
REV
Options:
AUXOUT
DIS
DIS
DIS
DIS
DIGIN1
NONE
NONE
NONE
NONE
DIGIN2
NONE
NONE
NONE
NONE
Communications:
ComADR
20
20
20
20
ComSTA
MODB
MODB
MODB
MODB
BAUD
19.2K
19.2K
19.2K
19.2K
TX_DLY
1
1
1
1
WS FLT
FP B
FP B
FP B
FP B
SDENAB
DIS
DIS
DIS
DIS
UNITS
ENG
ENG
ENG
ENG
Alarms:
A1S1TY
PROC
PROC
PROC
PROC
A1S1VA
300
300
500
500
A1S1HL
HIGH
HIGH
HIGH
HIGH
A1S2TY
NONE
NONE
NONE
NONE
A2S1TY
NONE
PROC3
NONE
PROC3
A2S1VA
NONE
50
NONE
50
A2S1HL
NONE
LOW
NONE
LOW
A2S2TY
NONE
NONE
NONE
NONE
ALHYST
0
0
0
0
ALARM1
NoLATCH
NoLATCH
NoLATCH
NoLATCH
BLOCK
DIS
DIS
DIS
DIS
DIA AL
DIS
DIS
DIS
DIS
Display:
DECMAL
ONE
ONE
ONE
ONE
TUNITS
F
F
F
F