3.2.2 Three principles on refrigerant piping work
In case of using refrigerant R410A in the refrigeration cycle, the refrigeration oil should be of a synthetic type one.
In order to avoid oxidation, pay much careful attention to basic piping work control to avoid infiltration of moisture or dust
during the refrigerant piping work.
Three principles
Cause of failure
Presumable failure
Preventive action
1. Dry
Keep good dryness
•
Water infiltration due to insufficient
protection at pipe ends
Icing inside tube at ex. valve
(Water choking)
Pipe protection
+
1 Pinching
•
Dewing inside of pipes
Generation of hydration and oxidation
of oil
2 Taping
↓
↓
•
Insufficient vacuum pumping time
Clogged strainer, etc., insulation failure
and compressor failure
Flushing
↓
Vacuum Drying
•
One gram of water turns into gas
(approx. 1000 lrs) at 1 Torn
•
Therefore, it takes long time to
vacuum-pump by a small vacuum
pump
2. Clean
No dust inside of pipes
•
Infiltration of dust or other through
the pipe ends.
•
Oxidation film during brazing
without blowing nitrogen.
•
Insufficient flushing by nitrogen
after brazing
Clogging of expansion valve, capillary
tube and filter
Pipe Protection
→
Oxidation of oil
1 Mounting Caps
→
Compressor failure
2 Taping
↓
3 Pinching
Insufficient cooling or heating
compressor failure
↓
Flushing
3. No leakage
No leakage shall exist
•
Brazing failure
Refrigerant shortage
Careful Basic Brazing Work
→
Performance decrease
↓
•
Failed flaring work and insufficient
torque of squeezing flare
→
Oxidation of oil
Basic Flaring Work
→
Overheating of compressor
↓
•
Insufficient torque of squeezing
flanges
↓
Basic Flange Connecting Work
Insufficient cooling or heating
compressor failure
↓
Air Tight Test
↓
Holding of Vacuum
3.2.3 Suspension of refrigerant piping
Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching weak parts of the building
such as walls, ceiling, etc. (If touched, abnormal noises may occur due to the vibration of the piping. Pay special attention
in case of short piping length).
A. Fire-proof section treatment.
B. Indoor unit.
In order to fix the piping to wall or ceilings use suspension and clamping systems as shown in the following figure.
3 Piping work and
refrigerant charge
54
SMGB0060 rev. 1- 12/2010
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......