Phenomenon
Cause
Check item
Action
(Turn OFF Main Switch)
Activation of High Pressure Switch
due to Excessively High Discharge
Pressure during Heating Operation
Insufficient Air Flow to Heat
Exchanger of Indoor Unit
Clogging of Heat Exchanger
Remove it
Check for dust on air filter
Check for any obstacle at inlet or
outlet of heat exchanger
Check the service space
Secure service space
Check for fan speed.
(Cooling: Outdoor Fan Heating:
Indoor Fan)
Replace fan motor if faulty
Activation of High Pressure Switch
due to Excessively High Discharge
Pressure during Heating Operation
Excessively High Temp. Air to
Indoor Unit Heat Exchanger
Calculate heat load.
Reduce heat load or use a bigger
unit
Check for hot air near the ceiling
Make good circulation
Check for short circuited air
Remove short-circuited air
Check for other heat source
Remove heat source
Faulty High
Pressure Switch
Faulty Pressure
Switch
Measure discharge pressure.
Check continuity after decreasing
of pressure
Replace it if faulty
Insufficient
Contacting
Measure resistance by tester
Repair looseness.
Replace connector
Incorrect
Connection
Check connections
Repair connections
Faulty of Outdoor Fan Control
Check decreasing air flow volume
at pressure switch for control
activative
Replace thermistor for evaporating
temp. if faulty
Faulty of Pressure Switch for
Control
Check activated pressure and
connecting wire
Replace it if pressure switch for
control is faulty
Overcharged Refrigerant
Check cycle operating temp.
Charge refrigerant correctly
Mixture of Non-Condensable Gas in
Refrigerant Cycle
Check ambient temp. and pressure
Recharge refrigerant after vacuum
pumping
Clogging of Discharge Piping
Check for clogging
Remove clogging
Faulty or Malfunction of Expansion
Valve
Check for clogging
Remove clogging
Check connecting wiring and
connectors
Replace connector
Check operating sound from coil
Replace coil
Check discharge gas thermistor
Replace thermistor
Check attaching state of discharge
gas thermistor
Reattach thermistor
Liquid Line Stop Valve or Gas Line
Stop Valve are not in Operation
Check stop valves
Fully open stop valve
N O T E
This alarm code is indicated when the outdoor unit protective device is activated by high discharge pressure during
heating operation. Accordingly, when this alarm code is indicated, there is high possibility of high pressure switch
actuation and the above troubleshooting actions are based on such cases.
8 Troubleshooting
262
SMGB0060 rev. 1- 12/2010
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......