8.2.5 Cause of inverter stoppage
Code
Cause
Cause of Stoppage
for Corresponding
Unit
Remark
Indication
during Retry
Alarm Code
1
Automatic Stoppage of Transistor Module
(DIP-IPM Error)
(Overcurrent, Undercurrent, Temperature increase)
17
P7
53
2
Instantaneous Over Current
17
P7
48
3
Abnormal Inverter Fin Thermistor
17
P7
54
4
Electronic Thermal Activation (Inverter overcurrent)
17
P7
48
5
Inverter Voltage Decrease (Undervoltage)
18
P8
06
6
Over Voltage
18
P8
06
7
Abnormal Inverter Transmission
18
8
Abnormal Current Detection
17
P7
51
9
Instantaneous Power Failure Detection
18
11
Reset of Micro-Computer for Inverter
18
12
Earth Fault Detection from Compressor
(Only Starting)
17
P7
53
13
Phase detection abnormality
18
14
Inverter Non-Operation
18
55
15
Inverter Non-Operation
18
55
16
Inverter Non-Operation
18
P8
55
17
Communication Abnormality
18
P8
55
18
Protection Device Activation (63H1)
02
19
Protection Detection Device Abnormality
38
Protection control code on 7-segment display
1
Protection control code is displayed on 7-segment when a protection control is activated.
2
Protection control code is displayed while function is working, and goes out when released.
3
When several protection control are activated, code number with higher priority will be indicated (see below for the
priority order).
a
Higher priority is given to protection control related to frequency control than the other.
•
Priority order
– High-Pressure Increase Protection
– Over Current Protection
– Cold Draft Protection
– Low-Pressure Ratio Control at Cooling Operation
b
In relation to retry control, the latest retrial will be indicated unless a protection control related to frequency control
is indicated.
Code
Protection Control
P
0
Low-Pressure Ratio Control at Cooling Operation
P
1
High-Pressure Ratio Control at Heating Operation
P
2
High-Pressure Increase Protection
P
3
Over Current Protection
P
4
IPM Fin Temperature Increase Protection
P
5
Discharge Gas Temperature Increase Protection
8 Troubleshooting
295
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......