Check list on compressor
CLIENT:
MODEL:
DATE:
Serial N°:
Production date:
Checker:
N°
Check item
Check method
Result
Remarks
1
Is THM9 correctly connected?
THM9: Discharge gas thermistor
(1) Is wire of thermistor correctly connected by
viewing?
(2) Check to ensure the 7-segment indication of
Td when comp. is operating.
Td: Temperature of THM9
2
Is thermistor THM9 disconnected?
(1) Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
(2) Check to ensure that actually measured
temp. is the same as the indication during check
mode.
3
Is current sensor faulty?
(1) Check to ensure that indication A1 and A2
are 0 during compressor stopping.
(2) Check to ensure that indication A1 and A2
are not 0 during compressor running.
4
Is current sensing part on PCB2
faulty?
5
Is the direction of current sensor
(CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and V
inserted correctly into current
sensor?
Check to ensure that wires are correctly
inserted.
7
Is exp. valve (MV1) correctly
connected?
Check to ensure that MV1 to CN5A is correctly
connected.
8
Is exp. valve (MV1) coil correctly
connected?
Check to ensure that each coil is correctly
mounted on the valve.
9
Are the refrigeration cycle and
electrical wiring system incorrectly
connected?
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
10
Is opening of exp. valve completely
closed (locked)?
Check the following by the check mode of
outdoor units.
(1) Liquid pipe temp. (TL) < air intake temp.
(Ti) during cooling operation
(2) Liquid pipe temp. (TL) > air intake temp.
(Ti) during heating operation
11
Is opening of exp. valve fully opened
(locked)?
Check to ensure that liquid pipe temp. is lower
than air intake temp. of stopping indoor unit
when other indoor units are operating under
cooling operation
12
Are the contacts for comp. magnetic
switch CMC1 faulty?
Check the surface of each contact (L1, L2 and
L3) by viewing.
13
Is there any voltage abnormality
among L1-L2, L2-L3 and L3- L1?
Check to ensure that voltage imbalance is
smaller than 3%. Please note that power source
voltage must be within 380V or 220V+10%.
14
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
7 Test Run
187
SMGB0060 rev. 1- 12/2010
7
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......