
8.1.3 Abnormal transmission between the remote control switch and the indoor unit
•
RUN LED on the remote control switch:
Flickering every 2 seconds.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Disconnection or insufficient contacting of the remote control cable
Check the cable and the
connections
Repair the cable or connect the
cable
Failure of the remote control switch
Check the remote control switch by
means of the self-check mode *1)
Replace the remote control switch if
the remote control switch is faulty
Failure of PCB (in the indoor unit
and the remote control switch)
Disconnected wire to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
, see on page 301.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
, see on page
299.
8.1.4 Abnormal operation of the devices
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
RUN LED is ON and the
LCD is indicated.
However, the system
does not operate (For
example, the indoor fan,
the outdoor fan or the
compressor does not
operate)
Failure of the indoor unit
fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the Indoor unit fan motor
Burnt-out coil
Measure the insulation
resistance
Failure of the outdoor
unit fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the outdoor unit fan
motor
Burnt-out coil
Measure the insulation
resistance
Failure of the magnetic
switch for the outdoor
unit fan motor
Insufficient contacting
Measure the voltage between
the contacting parts
Replace PCB for the outdoor unit
Failure of the comp. motor
Measure the resistance between
two wires
Replace the compressor
Failure of the comp.
Check for an abnormal sound
from the Comp.
Failure of the magnetic
switch for comp.
Insufficient contacting
Check that the magnetic switch
activates correctly or not
Replace the magnetic switch
Failure of one of PCBs
Disconnected wiring to
PCB
Check the connections
Correctly connect the wiring
Failure of PCB
Check PCB by means of the self-
check mode *1)
Replace PCB if it failed
8 Troubleshooting
198
SMGB0060 rev. 1- 12/2010
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......