Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Cooling or heating
process with an
abnormal sound
Foreign particles inside of the fan casing
Visually inspect it
Remove the foreign particles
Indoor unit fan runner is hitting the casing
Visually inspect it
Adjust the position of the fan
runner
Outdoor unit propeller fan is hitting the shroud
Visually inspect it
Adjust the position of the
propeller fan
Abnormal sound from
the compressor
Faulty Installation
Check that each part is tightly
fixed
Tightly fix each part
Liquid ref. compression
Adjust the suction gas temp. and
pressure
Ensure superheat
Wear or breakage of the
internal comp. parts
Abnormal Sound from the Inside
of the Compressor
Replace the compressor
No heating by the oil
heater
Check the Resistance (Oil
Heater, Fuse)
Replace the oil heater or the fuse
Humming sound from the magnetic conductor
Check the surface of the
contacts
Replace the magnetic switch
Abnormal vibration of the cabinets
Check each fixing screw
Tightly fix each screw
Outdoor fan does not
operate when the
compressor operates
Obstacle at the outdoor fan
Check the obstacles
Remove the obstacles
Watching condition for the heating process
Wait for the switching of the 4-
Way Valve (1 ~ 3 minutes)
If the 4-Way Valve does not
switch, check for insufficient
refrigerant
Indoor fan does not
operate when the
compressor operates
Discharge pressure does not increase higher than
1.5 Mpa due to the insufficient refrigerant
Check the operation pressure *5)
Add the refrigerant
Disconnected Wiring for the Indoor Fan
Check the wiring
Connect the wiring correctly
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
, see on page 301
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
, see on page
299.
•
*3): Even if the remote control switches are normal, the compressor does not operate under the following
conditions:
1 Indoor temp. is lower than 21 °C or outdoor temp. Is lower than -5 °C during the cooling process (DB).
2 Indoor temp. is higher than 27 °C (DB) or outdoor temp. is higher than 15 °C (WB) during the heating process.
3 When a cooling (or heating) process signal is given to the outdoor unit and a different mode as heating (or
cooling) process signal is given to the indoor units.
4 When an emergency stop signal is given to outdoor unit.
•
*4): Refer to chapter 7 of “Technical Catalogue”.
•
*5): Refer to chapter 10 of “Technical Catalogue”.
8 Troubleshooting
203
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......