4.5 Wire sizes
4.5.1 Wire sizes for IVX Series
Field minimum wire sizes for the power source
Model
Power Source
Max. Current (A)
Power Source Cable Size
Transmitting Cable Size
EN60 335-1 (2*)
EN60 335-1 (2*)
All Indoor Units (1*)
230V/1φ/50Hz
5
0.75 mm
2
0.75 mm
2
RPI-8-10
10
1.5 mm
2
RAS-3HVRNME
230V/1φ/50Hz
14
2.5 mm
2
RAS-4HVRNM1E
18/24
4.0 mm
2
RAS-5HVRNM1E
26
6.0 mm
2
RAS-6HVRNM1E
26
6.0 mm
2
RAS-4HRNM1E
400V/3φ/50Hz
7
2.5 mm
2
RAS-5HRNM1E
11
2.5 mm
2
RAS-6HRNM1E
13
2.5 mm
2
RAS-8HRNME
13.2
2.5 mm
2
RAS-10HRNME
17.1
4.0 mm
2
RAS-12HRNME
21.2
4.0 mm
2
N O T E
•
(1*): Except RPI-8.0-10.0
•
Follow local codes and regulations when selecting field wires.
•
The above wire sizes marked with (2*) are selected at the maximum current of the unit according to the European
standard, EN60 335-1. Use wires not lighter than the ordinary neoprene (polychloroprene) sheathed flexible
cord (code designation H05RN-F).
•
In the case that the power cables are connected in series, add each unit maximum current and select the wire
sizes in next table.
•
The ground cable size must comply local code: IEC 245, No. 571.
4 Electrical Wiring
95
SMGB0060 rev. 1- 12/2010
4
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......