12.7 Caution with the refrigerant leakage
The designers and the installers have the responsibility to follow the local codes and the local regulations that specify the
safety requirement against the refrigerant leakage.
12.7.1 Maximum permissible concentration of the HCFC gas
The refrigerant R410A, which is charged in the UTOPIA IVX/ES system, is an incombustible non-toxic gas. However, if the
leakage occurs and the gas fills a room, the gas may cause suffocation.
The maximum permissible concentration of the HCFC gas and the R410A in the air is 0.44 kg/m
³
, according to the
refrigeration and air conditioning system standard (KHK S 0010) by the KHK (high-pressure gas protection association) of
Japan. Therefore, you must take some effective measures in order to lower the R410A concentration in the air below 0.44
kg/m
3
, if there is a leakage.
12.7.2 Calculation of the refrigerant concentration
1
Calculate the total quantity of refrigerant R (kg) that is charged in the system that connects all the indoor units of the
rooms that need air conditioning systems.
2
Calculate the room volume V (m
³
) of each room.
3
Calculate the refrigerant concentration C (kg/m
³
) of the room according to the following equation:
C = R/V
R: Total quantity of charged refrigerant (kg)
V: Room volume (m
³
)
C: Refrigerant concentration (
≤
0.44* kg/m
3
for the R410A)
* Use this value only for reference because this value is not fixed yet.
12.7.3 Countermeasure for the refrigerant leakage according to the KHK standard
According to the KHK standards, you should arrange the facility as follows so that the refrigerant concentration will be bellow
0.3 kg/m
3
.
1
Provide a shutterless opening that will allow the fresh air to circulate into the room.
2
Provide a doorless opening with a size of 0.15% or more to the floor area.
3
Provide a ventilator, which must be linked with a gas leak detector, with a ventilating capacity of 0.5 m
3
/min or more per
Japanese refrigeration ton (=compressor displacement 8.5 m
3
/h of the air conditioning system which uses the
refrigerant).
•
IVX
O.U. model
Ton
RAS-8HRNM
2.49
RAS-10HRNM
3.32
RAS-12HRNM
4.15
•
ES
O.U. model
Ton
RAS-(2-2.5)HVRN1(E)
0.88
RAS-3HVRNS
1.14
RAS-4HVRNS1E
1.67
RAS-(5-6)HVRNS1E
2.27
RAS-8HRNSE
2.49
RAS-10HRNSE
3.32
4
Pay a special attention to the place, such as a basement and others, where the refrigerant may stay, because the
refrigerant is heavier than the air.
12 Maintenace notes
464
SMGB0060 rev. 1- 12/2010
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......