8.1.2 Failure of the power supply to the indoor unit and the remote control switch
•
The LED and the LCD are not indicated.
•
Not operated
If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means of
the voltmeter
Supply the power
Blown out fuse or activation of the
breaker at the power source
Short circuit supplied between the
wires
Check for any uncovered part of the
wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the wires to earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure resistance between wires
and insulation resistance
Replace the fan motor and fuse
Blown out fuse at the control circuit
Short circuit supplied between the
wires
Check for any uncovered part of the
wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the control circuit to
earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of the transformer at the indoor unit side
Measure the voltage at the
secondary side
Replace the transformer
Disconnected cable of the remote control switch
Connect the cable
Replace the cable or repair the
cable
Insufficient contacting at the
connectors of the remote control
switch
Insufficient connection or incorrect
connection of the indoor unit PCB
Check the connectors
Correctly connect the connector
Insufficient connection or incorrect
connection of the indoor unit PCB in
the remote control switch
Failure of the remote control switch
Check the remote control switch by
means of the self-check mode *1)
Replace the remote control switch if
it failed
Failure of PCB
Unconnected wires to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in "TEST RUN"
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
, see on page 301.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
, see on page
299.
8 Troubleshooting
197
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......