Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Insufficient heating
process
Indoor heat load is greater than the heating capacity
Calculate the heat load
Replace the unit with a bigger unit
Excessively low suction
pressure
Gas leakage or
insufficient refrigerant
charge
Measure superheat
Correctly charge the refrigerant
after the gas leakage check and
repairing
Excessively small
diameter or long piping
Measure the field supplied piping
Use the specified pipes
Failure or malfunction of
the expansion valve
Check for clogging
Remove the clogging
Check the connection cord and
the connector
Replace the connector
Is there an operation sound from
the coil?
Replace the coil
Is the thermistor on the
compressor normal?
Replace the thermistor
Is the thermistor installed
correctly on compressor?
Correctly install the thermistor
Clogging of I.U./O.U.
strainer
Check the temp. difference
between the inlet and the outlet
of strainer
Replace the strainer for the
outdoor unit or the indoor unit
Clogging of suction
piping
Check the temp. difference of
each part
Remove the clogging
Insufficient air flow
through the outdoor unit
heat exchanger
Is the outdoor unit heat
exchanger clogged?
Remove the clogging
Are there any obstacles at the
inlet or the outlet of outdoor unit?
Remove the obstacles
Is the service area for the
outdoor unit sufficient?
Secure a sufficient service area
Check the speed of the outdoor
unit fan
Replace the fan motor
Excessively low air
temp. through the
outdoor unit heat
exchanger
Check for any short-circuited air
to the outdoor unit
Remove the cause of the short-
circuited air
Defrosting is
insufficiently completed
Check the thermistor for the
defrost operation
Replace the thermistor for the
defrost operation
Excessively high
discharge pressure
Insufficient air flow to the
indoor unit heat
exchanger
Check the filter for a clogging
Remove the clogging
Check for any obstacles at the
inlet or the outlet of the indoor
unit
Remove the obstacles
Check the indoor fan speed
Replace the fan motor
Excessively high air
temp. to the indoor unit
heat exchanger
Check whether or not the short-
circuited air exists
Remove the cause of the short-
circuited air
Excessively charged
refrigerant
Check the refrigerant quantity *4)
Correctly charge the refrigerant
Non-condensate gas in
ref. cycle
Check the refrigerant quantity *4)
Recharge the refrigerant after the
vacuum pumping
Clogging of the
discharge pr. piping
Check for clogging
Remove the clogging
Malfunction or internal leakage of the 4-way valve
Check the temp. difference at the
inlet and the outlet of the 4-way
valve
Replace the 4-way valve
Malfunction of the check valve of the outdoor unit
Check the temp. difference at the
inlet and the outlet of the check
valve
Replace the check valve
Excessively high suction
pressure
Malfunction or internal
leakage of 4-way valve
Check the temp. difference at the
inlet and the outlet of the 4-way
valve
Replace the 4-way valve
Discharge temp. of the indoor unit is unstable
Check the expansion valve of the
indoor unit in the same system
Replace the failed expansion
valve of the indoor unit
8 Troubleshooting
202
SMGB0060 rev. 1- 12/2010
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......