Phenomenon
Cause
Check item
Action
(Turn OFF the main
switch)
Activation of the high-
pressure switch due to the
excessively high discharge
pressure
Insufficient Air Flow to the Heat Exchanger (Outdoor Heat
Exchanger during the Cooling Process or Indoor Heat
Exchanger during the Heating Process)
Check the heat exchanger
for dust or for clogging
Remove the dust or the
clogging
Check the air filter for dust
Remove the dust
Check for any obstacles at
the inlet or the outlet of the
heat exchanger
Remove the obstacles
Check the service area
Secure service area
Check the speed (Outdoor
Fan: Cooling / Indoor Fan:
Heating)
Replace the fan motor if
faulty
Malfunction of the Expansion Valve
Disconnected of the
Connector
Fix the looseness or
reconnect the connector
Fully closed and locked
Replace the expansion
valve
Excessively High Temp. Air to the Indoor Unit
Calculate the heat load
Reduce the heat load or use
a bigger unit
Check for hot air near the
ceiling (Heating)
Provide good circulation
Check for short-circuited air
(Heating)
Remove the short-circuited
air
Check for other heat source
Remove the heat source
Faulty High-Pressure
Switch
Faulty Pressure Switch
Measure the discharge
pressure. Check the
continuity after the decrease
of the pressure
Replace the pressure switch
if faulty
Insufficient Contacting
Measure the resistance by
means of the tester
Fix the looseness. Replace
the connector
Incorrect Connection
Check the connections
Repair the connections
Activation of the high-
pressure switch due to the
excessively high discharge
pressure
Faulty or malfunction of the expansion valve
Check for clogging
Remove the clogging
Check the connect wiring
and the connectors
Replace the connector
Check the operation sound
from the coil
Replace the coil
Check the discharge gas
thermistor
Replace the thermistor
Check the attaching state of
the discharge gas
thermistor
Reattach the thermistor
Faulty gas bypass solenoid valve
Check for clogging
Replace the gas bypass
solenoid valve
Overcharged refrigerant
Check the cycle operation
temp.
Charge the refrigerant
correctly
Mixture of the non-condensate gas in the refrigerant cycle
Check the air temp. and the
pressure
Recharge the refrigerant
after the vacuum pumping
Clogging of the discharge piping
Check for clogging
Remove the clogging
Liquid line stop valve or gas line stop valve is not in
operation
Check the stop valves
Fully Open the stop valves
Clogging of the check valve
Check for clogging
Replace the check valve
8 Troubleshooting
209
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......