The activating conditions of protection control are shown in the table below
Code
Protection Control
Activating Condition
Remarks
P0
Low-Pressure Ratio Control at Cooling
Operation
Compression Ratio ε < 2.2
=> Frequency Increase
ε = (Pd+0.1)/(Ps+0.1)
P1
High-Pressure Ratio Control at Heating
Operation
Compression Ratio ε > 7.5
=> Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
P2
High-Pressure Increase Protection
High Pressure Switch for Control is activated
=> Frequency Decrease
—
P3
Over Current Protection
Inverter Output Current > (*1)A
=> Frequency Decrease
—
P4
DIP-IPM, ISPM or IPM Temperature
Increase Protection
Inverter Fin Temperature
RAS-8~10HRNSE > 100 ºC
RAS-3~6HVRNS(E) > 80 ºC
=> Frequency Decrease
—
P5
Discharge Gas Temperature Increase
Protection
Temperature at the top of compressor is high
=> Frequency Decrease
Temperature at the top of compressor > 107 ºC
=> Indicate P5
—
P6
Frost Formation Protection
TL
≤
2 °C Over 3 minutes => Frequency Decrease
TL: Liquid Piping,
Temperature of Indoor Unit
P9
Unbalance Power Source Detecting
Inverter Output Current > (*3)A
=> Frequency Decrease
—
P
Current Demand Control
Inverter Output Current > (*2)A
=> Frequency Decrease
In case of
Demand Control Setting
Pb
Low-Pressure Decrease Protection
Low Pressure Switch for Control is activated.
=> Frequency Decrease
—
PC
Cold Draft Protection
TO
≤
10 ºC and ε
≥
2.6 => Frequency Decrease
ε = (Pd+0.1)/(Ps+0.1)
TO: Outlet Temperature of
Indoor Unit
P7
Inverter Retry
Automatic Stoppage of Transistor Module,
Activation of Electronic Thermal or Abnormal Current
Sensor
When activating 3 times in 30
minutes, “48”, “51”, “53” or “54”
alarm is indicated.
P8
Inverter Retry
Insufficient/Excessive Voltage at Inverter
Circuit or PCB Connector Part
When activating 3 times in 30
minutes, “06” or “55” alarm is
indicated.
N O T E
•
During protection control (except during alarm stoppage), the protection control code is indicated.
•
The protection control code is indicated during protection control and turns off when cancelling the protection
control.
•
After retry control, the condition of monitoring is continued for 30 minutes.
•
The Maximum value of IVX series (*1) and (*2) are as follows:
•
The Maximum value of ES series (*3), (*4) and (*5) are as follows:
(1*)
HP
380-415V
220-240V
4
5
6
8
10
12
3
4
5
6
Current (A)
8.0
12.0
12.0
17.5
20.0
21.0
16.0
16.0
24.0
24.0
(2*)
HP
380-415V
220-240V
Demand setting
4
5
6
8
10
12
3
4
5
6
Current (A)
100%
4.0
5.5
20.0
8.5
10.0
12.0
11.5
13.0
17.0
20.0
75%
3.0
4.0
15.0
6.0
8.0
12.0
8.5
10.0
13.0
15.0
50%
2.0
2.0
10.0
4.0
5.0
7.5
5.5
6.5
8.5
10.0
8 Troubleshooting
297
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......