Alarm codes for IVX and ES Series
Code
No.
Category
Type of Abnormality
Main cause
01
Indoor unit
Activation of protection device
Failure of fan motor, drain discharge, PCB, relay, float switch
activated.
02
Outdoor unit
Activation of protection device
Activation of PSH, locked motor, abnormal operation in the
power supply phase.
03
Transmission
Abnormality between indoor (or outdoor) and outdoor
(or indoor) units
Incorrect wiring. Failure of PCB. Tripping of fuse. Power supply
OFF.
04
Abnormal operation between inverter and control PCB
Transmission failure between inverter PCBs
05
Power supply
Abnormal power supply
Power source with abnormal wave pattern.
06
Voltage drop
Voltage drop due to excessively low or high voltage in
outdoor unit
Voltage drop in power supply. Incorrect wiring or insufficient
capacity of power supply wiring.
07
Cycle
Drop in discharge gas overheating
Excessive refrigerant charge. Expansion valve lock open.
08
Increase in discharge gas temperature
Insufficient refrigerant charge, refrigerant leakage. Expansion
valve closed or clogged.
11
Sensor in indoor
unit
Inlet air thermistor
Failure of thermistor, sensor, connection.
12
Outlet air thermistor
13
Anti-freeze thermistor
14
Gas pipe thermistor
15
Fresh Outdoor Air Thermistor (Econofresh)
19
Protection device for fan motor is triggered
Failure of fan motor
20
Outdoor unit
sensor
Compressor thermistor
Failure of thermistor, sensor, connection.
22
Outside air thermistor
24
Evaporation thermistor
31
System
Incorrect setting of outdoor and indoor units
Incorrect setting of capacity code.
35
Incorrect setting of indoor unit number
Duplication of indoor unit number.
38
Abnormality of protective circuit in outdoor unit
Failure of indoor unit PCB; incorrect wiring; connection to
indoor unit PCB.
41
Pressure
Cooling overload (possible activation of high pressure
device)
O.U. pipe thermistor temp. is higher than 55 ºC and the
compressor top temp. is higher than 95 ºC, O.U. protection
device is activated.
42
Heating overload (high-pressure device may be
activated)
If I.U. freeze protection thermistor temp. is higher than 55 ºC
and compressor top temp. is higher than 95 ºC, O.U. protection
device is activated.
47
Activation of protection device for low pressure drop
Stoppage due to excessive decrease of evaporating
temperature (Temp < -35 ºC) is activated 3 times in one hour,
motor locked in heating mode.
48
Inverter
Activation of overcurrent protection
Overload, overcurrent. Failure of DIP IPM, IPM or PCB2, heat
exchanger clogged, locked compressor.
51
Abnormality in inverter current sensor
Incorrect wiring of current sensor. Failure of control PCB, DIP
IPM, IPM or PCB2.
52
Abnormal thermistor of inverter fin (for inverter fin
temperature)
Shorcircuit or incorrect wiring
53
Activation for protection of DIP IPM, IPM or PCB2
Abnormality of DIP IPM or PCB2
Compressor failure, heat exchanger clogged.
54
Increase in inverter fin temperature
Abnormal inverter fin thermistor
Heat exchanger clogged.
Abnormal outdoor fan.
55
Abnormality of DIP IPM, IPM or PCB2
Failure of DIP-IPM, IPM or PCB2.
57
Outdoor fan
Fan motor abnormality
Disconnected wire or incorrect wiring between control PCB
and inverter PCB.
Incorrect wiring or abnormality in fan motor.
59
Inverter
Abnormal inverter fin thermistor (for the temperature of
inverter fin)
Lost terminals, disconnected wire, failure of inverter thermistor.
EE
Compressor
Compressor protection alarm
Compressor failure.
8 Troubleshooting
205
SMGB0060 rev. 1- 12/2010
8
Summary of Contents for RAS-10HRNM
Page 2: ......
Page 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Page 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Page 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Page 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Page 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Page 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Page 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Page 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Page 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Page 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Page 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Page 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Page 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Page 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Page 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Page 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Page 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Page 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Page 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Page 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Page 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Page 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Page 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Page 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Page 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Page 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Page 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Page 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Page 481: ......