4-43
Chapter 4
For parameter configuration
[CE101]
~
[CE107]
Low-current detection signal
Code/Name
Range (unit)
Initial value
CE101
Low-current
indication signal mode
selection, 1st-motor
00(During Acc/Decel and
constant-speed operation)
01(only during
constant-speed operation)
01
CE102
Low-current detection
level 1, 1st-motor
Inverter rated
current×(0.00
~
2.00)
Inverter
rated current
×1.00
CE103
Low-current detection
level 2, 1st-motor
Inverter rated
current×(0.00
~
2.00)
Inverter
rated current
×1.00
・
In the case of low-current, outputs a signal.
Overload detection signal
Code/Name
Range (unit)
Initial value
CE105
Overload warning signal
mode selection, 1st-motor
00(During Acc/Decel
and constant speed)/
01(During
constant
speed only)
01
CE106
Overload
warning level 1, 1st-motor
Inverter rated
current×(0.00
~
2.00)
Inverter
rated current
×1.00
CE107
Overload
warning level 2, 1st-motor
Inverter rated
current×(0.00
~
2.00)
Inverter
rated current
×1.00
・
In the case of overload, outputs a signal.
[CE-10]
~
[CE-31]
Frequency arrival signal
Code/Name
Range
(unit)
Initial
value
CE-10
Arrival frequency for acceleration 1
0.00
~
590.00(Hz)
0.00
CE-11
Frequency arrival for deceleration 1
0.00
CE-12
Arrival frequency for acceleration 2
0.00
CE-13
Frequency arrival for deceleration 2
0.00
・
Sets the operation of the arrival signal.
(Example) In FA2/FA4 case:
(Example) In FA3/FA5 case:
Over-torque signal
Code/Name
Range (unit)
Initial
value
CE120
Over-torque level (Forward
during), 1st-motor
0.0
~
300.0(%)
100.0
CE121
Over-torque level (Reverse
driving), 1st-motor
100.0
CE122
Over-torque level (Forward
regenerative), 1st-motor
100.0
CE123
Over-torque level (Forward
driving), 1st-motor
100.0
・
Sets the level to output the 019[OTQ] signal, when using
vector control and the torque goes over the limit.
Electronic thermal warning
Code/Name
Range
(unit)
Initial
value
CE-30
Electronic thermal level (motor)
0.00
~
100.00(%)
80.00
CE-31
Electronic thermal level (inverter)
80.00
・
Sets the level to output the motor electronic thermal
warning 026[THM].
・
Sets the level to output the inverter electronic thermal
warning 027[THC].
Output current(A)
Low-current
indication signal
detection level
[CE102]/[CE103]
[LOC]/[LOC2]
indication signal
ON
ON
Overload warning
level [CE106]/[CE107]
Output current
OL/OL2 output
fon
:
Maximum frequency 1%
foff
:
Maximum frequency 2%
[CE-10]/[CE-12]
[CE-11]/[CE-13]
f
on
f
off
Output
frequency
FA2/FA4
fon
:
Maximum frequency 1%
foff
:
Maximum frequency 2%
f
on
f
on
f
off
f
off
[CE-11]/[CE-13]
[CE-10]/[CE-12]
Output frequency
FA3/FA5