2.7 Applicable circuit breaker
200V class
•
For ND rating
•
For LD/VLD rating
Device model name on above table shows example selection. The
device selection should be made in base on rated current, short
circuit current capability and accordance to the local electrical
legislation.
Applicable motor capacity is based on Hitachi 200Vac, 60Hz, 4 pole
IE3 motor.
Refer to the wire gauge table on chapter 2-8 for power line cable.
Electrical endurance for AC-1 magnetic contactor is 500000 times,
however, for emergency stop in motor operation will be only 25
times.
Select AC-3 class magnetic contactor for inverter output for
application which has an emergency stop or commercial power line
operation.
When selecting oversize inverter capacity compare to motor rating,
select magnetic contactor according to the inverter capacity
Model
P1-*******
(P1-****)
Applicable
Motor
(kW)
Applicable devices (Input Voltage 200
~
220V)
Without reactor
(DCL or ACL)
With reactor
(DCL or ACL)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Example
model
Current
Rate
AC-1
AC-3
Example
model
Current
Rate
AC-1
AC-3
P1-00044-L(P1-004L)
0.4
EB-30E
5
HS8
HS8
EB-30E
5
HS8
HS8
P1-00080-L(P1-007L)
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
P1-00104-L(P1-015L)
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
P1-00156-L(P1-022L)
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
P1-00228-L(P1-037L)
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
P1-00330-L(P1-055L)
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
P1-00460-L(P1-075L)
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
P1-00600-L(P1-110L)
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
P1-00800-L(P1-150L)
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
P1-00930-L(P1-185L)
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
P1-01240-L(P1-220L)
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
P1-01530-L(P1-300L)
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
P1-01850-L(P1-370L)
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
P1-02290-L(P1-450L)
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
P1-02950-L(P1-550L)
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
Model
P1-*******
(P1-****)
Applicable
Motor
(kW)
Applicable devices(Input Voltage 200
~
220V)
Without reactor
(DCL or ACL)
With reactor
(DCL or ACL)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Example
model
Current
Rate
AC-1
AC-3
Example
model
Current
Rate
AC-1
AC-3
P1-00044-L(P1-004L)
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
P1-00080-L(P1-007L)
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
P1-00104-L(P1-015L)
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
P1-00156-L(P1-022L)
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
P1-00228-L(P1-037L)
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
P1-00330-L(P1-055L)
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
P1-00460-L(P1-075L)
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
P1-00600-L(P1-110L)
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
P1-00800-L(P1-150L)
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
P1-00930-L(P1-185L)
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
P1-01240-L(P1-220L)
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
P1-01530-L(P1-300L)
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
P1-01850-L(P1-370L)
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
P1-02290-L(P1-450L)
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
P1-02950-L(P1-550L)
75
EX600B
500
H300C
H400C
EX400
400
H200C
H300C
Summary of Contents for P1-00041-H
Page 6: ...0 5 Contents Contents Memo ...
Page 42: ...2 26 Chapter 2 Installation and Wiring Memo ...
Page 129: ...Index Index 3 memo ...
Page 130: ...Index Index 4 memo ...