4-31
Chapter 4
For parameter configuration
[bb101]
~
[bb-42]
Reduction of electromagnetic sound
Code/Name
Range (unit)
Initial
value
bb101
Carrier
frequency, 1st-motor
0.5
~
16.0(kHz)
2.0
bb102
Sprinkle carrier
pattern selection,
1st-motor
00(Disable)/
01(Enable: Patern-1)/
02(Enable: Patern-2)/
03(Enable: Patern-3)
00
bb103
Automatic carrier
frequency reduction
selection, 1st-motor
00(Disable)/
01(Enable: Current)/
02(Enable: Temperature)
00
・
To decrease noise, [bb101] should be set small. To lower
electromagnetic sound, [bb101] has to be set bigger.
・
By setting the duty specification selection [Ub-03], the
carrier frequency is internally limited.
・
For the sake of the inverter protection, the Automatic
carrier reduction [bb103] decreases the carrier in
certain cases.
Reset operation after error event
Code/Name
Range (unit)
Initial
value
bb-10
Automatic
error reset selection
00(Disable)/
01(If RUN command is OFF)
02(After set time)/
04(Emergency force drive)
00
bb-11
Automatic
error reset wait time
00(Enable)/
01(Disable)
00
bb-12
Automatic
reset waiting time
0.0
~
600.0(s)
2.0
bb-13
Automatic
error reset number
0
~
10(count)
3
・
Adjustment of the automatic reset that follows an error
event. In the case that RUN command was on
execution, after the reset, is followed by the setting of
[bb-41].
Retry/trip setting in error event
Code/Name
Range (unit)
Initial
value
bb-20
Retry count after power loss
event
0
~
16/255
0
bb-21
Retry count after
undervoltage event
0
~
16/255
0
bb-22
Retry count after
overcurrent event
0
~
5
0
bb-23
Retry count after
overvoltage event
0
~
5
0
・
Sets number of retries before tripping.
・
If 0 is set, as soon as an error occurs, it will trip.
・
If you want to reset the retry count, assign any value
other than 0.
[bb-45]
~
[bb-59]
Code/Name
Range (unit)
Initial
value
bb-24
Selection of restart mode at
Instantaneous power failure/
under-voltage trip
*3)
00
bb-25
Allowable under-voltage
power failure time
0.3
~
25.0(s)
1.0
bb-26
Retry wait time before motor
restart
0.3
~
100.0(s)
1.0
bb-27
Instantaneous power
failure/under-voltage trip alarm enable
00(Disable)/
01(Enable)/
02(Disable at
Stop/Decel. stop)
00
bb-28
Selection of restart mode at
over-current
*3)
00
bb-29
Wait time of restart at
over-current
0.3
~
100.0(s)
1.0
bb-30
Selection of restart mode at
over-voltage
*3)
00
bb-31
Wait time of restart at
over-voltage
0.3
~
100.0(s)
1.0
*3) 00(Restart motor with 0Hz)/01(Restart with a matching
frequency)/02(Restart with active frequency matching)/03(Detect
speed)/04(Decelerate and stop with a matching frequency and then
trip)
・
Regarding the restart, after the waiting time is
completed the selected restart method is carried out.
Restart mode after FRS/RS
Code/Name
Range
(unit)
Initial
value
bb-40
Restart mode after FRS release
*4)
00
bb-41
Restart mode after RS release
00
*4) 00(Start with 0Hz)/01(Start with matching frequency)/02(Start with
active frequency matching)/03(Detect speed)/
・
When using Intelligent input terminals [FRS] and [RS],
restart mode can be selected.
・
[bb-40] allows you to select the restart operation after a
free-run stop.
・
[bb-41] allows you to select the restart operation after a
trip or reset event.
Minimum level of frequency matching
Code/Name
Range (unit)
Initial value
bb-42
Restart frequency
threshold
0.00
~
590.00(Hz)
0.00
・
The matching frequency function adopts the motor
frequency for a shockless start-up.
・
If at the restart the frequency is under the [bb-42]
frequency, a 0Hz restart will be used instead.
Retry wait time
Free-run (FRS)
Primary
cut off
Inverter
output
Motor speed
Lower limit
[bb-42]
Restart with matching
frequency