3-5
Chapter 3
Operation Setting and Examples of I/O Adjustment
Example for adjusting I/O terminals 1
3.9 Adjust the analog input (Ai1/Ai2)
E.g.) Adjust operation (E.g. for Ai1)
•
Set the ratio to input to limit the operating range of
the frequency command.
(When selecting the frequency through terminal input)
Parameter
Parameter
Details
Ai1
Ai2
[Cb-03]
[Cb-13]
Set the frequency source ratio to the
start ratio of the analog input.
[Cb-04]
[Cb-14]
Set the frequency source ratio to the
end ratio of the analog input.
[Cb-05]
[Cb-15]
Set the start ratio of the analog input 0
to 10V/0 to 20mA.
[Cb-06]
[Cb-16]
Set the end ratio of the analog input 0
to 10V/0 to 20mA.
•
Ai2 adjustment can be done in similar way to Ai1 by
using Ai2 parameters in order to Ai1.
E.g.) Make a fine adjustment (E.g. for Ai1)
Parameter
Parameter
Details
Ai1
Ai2
[Cb-30]
[Cb-32]
Adjust the zero-point reference line for
voltage input 10V/current input 20mA
and the maximum frequency.
[Cb-31]
[Cb-33]
Adjust the slope of the reference line
for voltage input 10V/current input
20mA.
*) Use the switch on control circuit terminal board to
change for voltage/current input.
Example for adjusting I/O terminals 2
3.10 Adjust the analog output
(Ao1/Ao2/FM)
E.g.) Adjust operation (E.g. for Ao1)
•
Set a value equivalent to 0% output first.
•
Then, adjust a value equivalent to 100% output.
Parameter
Parameter
Details
Ao1
Ao2
FM
[Cd-23]
[Cd-33]
-
Adjust the zero-point
reference line for voltage
output 10V/current output
20mA and data at 100%.
[Cd-24]
[Cd-34]
-
Adjust the slope for voltage
output 10V/current output
20mA and data at 100%.
-
-
[Cd-13]
Adjust the zero-point
reference line for 100%
duty cycle output and data
at 100%.
-
-
[Cd-14]
Adjust the slope for 100%
duty cycle output and data
at 100%.
Maximum
frequency
100%
[Cb-04]
[Cb-03]
0
[Cb-05]
[Cb-06]
100
(0V/0mA)
(10V/20mA)
Analog input
(V/mA)
While setting [Cb-07] = 00,
the frequency command
from 0% to [Cb-05] will be
set by [Cb-03].
100(%)
0
Parallel
slide
[Cb-30]=-50.0(%)
[Cb-30]=0.0(%)
Max.
0
50
-50
Change the
Slope angle
[Cb-30]=50.0(%)
[Cb-31]=200.0(%)
[Cb-31]=50.0(%)
[Cb-31]=100.0(%)
Output scale
t/T(%)
100
0
Parallel
slide
Output
range
[Cd-23]=50.0(%)
[Cd-23]=-50.0(%)
[Cd-23]=0.0(%)
Max.
0
50
-50
Full scale (FS)
t/T(%)
100
0
Output
range
[Cd-24]=200.0(%)
[Cd-24]=50.0(%)
[Cd-24]=100.0(%)
Max.
0
50
-50
[Cd-24]=-50.0(%)
Change the
slope
angle