5-2
Chapter 5
Troubleshooting
※
For others errors not shown above, refer to the user’s
guide.
■
Warning events
※
Regarding the warnings, please refer to the user’s guide.
Fixing the parameter details shown in the panel screen
may end the warning
5.2 Confirming the status
■
Frequently asked questions – FAQ (simplified edition)
Details of display
Code
Details
Corrective actions
Related parameter
E014
・
Ground fault detected at main
circuit voltage turning-on
・
Check for ground fault of the motor, wiring, etc.
-
E015
・
Continued state of incoming high
power
・
Review the power circumstances, such as the power
supply capacity
[dA-40]
E016
・
Instantaneous power failure,
control supply has dropped
・
If you wish to avoid the tripping, use the power loss retry
function.
[bb-20]
E019
・
Abnormality in temperature
detector circuit
・
Carry out counter measures for the inverter noise
-
・
Consecutive errors may cause a failure
-
E020
・
Because of cooling-fan life span,
internal temperature has raised
・
Change of the cooling-fan is necessary
-
・
Lower the carrier frequency
[bb101]
E021
・
Internal temperature has
increased
・
Requires a review of the installation circumstances
-
・
Lower the carrier frequency
[bb101]
E024
・
Disconnection of the wiring in the
supply side has occurred
・
Check the fastening of the input wiring with screws
-
・
Check that the 3 phases are correctly inserted
-
E030
・
Suddenly current increase
・
Output wiring ground fault
・
Disconnection confirm
-
・
Check that the motor is not locked
-
E034
・
Disconnection of the wiring in the
motor side has occurred
・
Check the output wiring disconnection, motor insulation
failure, …etc.
-
・
Check that the 3 phases are correctly inserted
-
E035
・
Abnormal motor temperature
・
Improve the motor cooling circumstances
-
・
Use the overload restriction function
[bA122]
・
Thermistor abnormality
・
Check for the break-down of the thermistor
-
・
Check the thermistor settings
[Cb-40]
E036
・
Brake abnormality
・
Check for the break-down of the brake and for the
disconnection of the wiring for the [BOK] signal
[dA-51]
・
Check the brake waiting time
[AF134][AF141]
E038
・
During slow speed, current has
increased
・
If torque is needed during slow speed, a review of the
inverter capacity is necessary
-
E040
・
Panel disconnection error
・
Check for the disconnection of the panel from the
inverter
[UA-20]
・
Noise counter-measures are necessary
-
E041
・
RS485 communication error
・
Noise counter-measures are necessary
-
・
Check the communication setting
[CF-01]
E042
・
RTC error
・
Battery replacement for the panel is necessary
-
E043
~
E045
E050
~
E059
・
There is an error in the EzSQ
programme.
・
For more information, please refer to the user’s guide.
E060
~
E089
・
There is an error in the option.
・
For more information, please refer to each option in
user’s guide.
E090
~
E093
・
There is an error in the STO path.
・
For more information, please refer to the P1 functional
safety guide.