30
Enforcer V10 Programming Guide
Walk Test Programming
Please note: Wireless detectors may take up to 5 minutes to become active in a walk test.
1.
Press
or
to scroll to ‘ENGINEER TESTS’. Press
.
2.
‘Sound to play’ will be displayed. Use [ or ] to select the different sounds. Press
to exit.
3.
‘Walk Test’ will be displayed. Press
.
4.
Select the areas that are required to be walk tested and press
or press
to walk test individual inputs.
5.
A list of all inputs programmed for that area will be displayed on the keypad.
Once an input has been walk tested (i.e. the detector has activated and
deactivated) then the input will be taken off the list.
6.
Once all inputs have been tested, ‘Walk Test Completed’ will be displayed. To
exit the walk test function at any time press
.
7.
Press
again to go back to the Engineer Menu.
Soak Control Programming
1.
Press
or
to scroll to ‘ENGINEER TESTS’. Press
.
2.
‘Sound to play’ will be displayed. Press
.
3.
‘Walk Test’ will be displayed. Press
.
4.
‘Soak Control’ will be displayed. Press
.
5.
Select the inputs that are required to be soak tested. Each input should be
entered, following by
. Press
once finished.
6.
‘Soak Days Left’ will be displayed. Select the number of days that the inputs
will be left on soak test and press
.
7.
‘Initial Soak’ will be displayed. Enter the number of days the soak test will revert
to in the event a soak input is triggered during testing. Press
.
8.
Press
to go back to the Engineer menu.
Test Siren, Battery Load Test and Outputs
1.
Press
or
to scroll to ‘ENGINEER TESTS’. Press
.
2.
‘Sound to play’ will be displayed. Press
.
3.
‘Walk Test’ will be displayed. Press
.
4.
‘Soak Test’ will be displayed. Press
.
5.
‘Test Siren’ will be displayed. Press
, any outputs programmed as ‘Siren
Any’ and ‘Strobe Any’ will trigger. Press
to exit.