Enforcer V10 Programming Guide
SYSTEM OPTIONS
Site Options
A full range of site options is available to tailor the operation of the system.
Set with Fault
If ‘YES’, the Enforcer will set regardless of the following faults being present: device fail, mains fail, battery fault, fuse
fault.
Set with Tamper
If ‘YES’, the Enforcer will set regardless of any input tampers.
Set with ATS Fault
If ‘YES’, the Enforcer will set regardless of the following ATS faults being present: telecom line fail, modem fail, ATE
path fail, Digi dial fail, or comms fail.
Set Fail = Alarm
If ‘YES’, the Enforcer will generate a graduated alarm when the ‘Set Fail’ timer has expired (See ‘CHANGE TIMERS’,) and
will trigger any output programmed as ‘0011 Set Fail’ if the setting procedure is still incomplete. If ‘NO’ the exit timer
will continue until the exit route is clear.
Do Battery Load Test
If ‘YES’, the Enforcer will perform a full battery load test at 7:00am each day.
Strobe/Squawk at Set
If ‘STROBE’, any output programmed as ‘STROBE ANY’ will activate for 5 seconds after the Enforcer has set. If ‘SQUAWK’
any output programmed as ‘SIREN ANY’ will activate for 5 seconds after the Enforcer has set, and if ‘BOTH’ then any
outputs programmed as STROBE ANY or SIREN ANY will activate for 5 seconds after the Enforcer has set.
Please note: If this function is enabled, a potential security risk could be in view for intruders to see.
Use Level Set
If ‘YES’: The system becomes a ‘level set’ (Having one area set only at any one time). If ‘NO’: The system becomes an
‘area’ system (setting more than once area at a time).
Autoset Force
If ‘YES’, and an auto set timer is programmed on the InSite upload/download software, then the Enforcer will set on
an auto set regardless of any inputs being open during the setting period.
Restrict PIN use
If ‘YES’, the Enforcer prevents a PIN code being entered on the Entry time, but allows a PIN code to silence any alarm
that may occur.
Please note: Enable when BS8243 option 6.4.5 is in use