IN-LINE STRAINER VALVE
CAUTION!
THE IN-LINE STRAINER/VALVE ASSEMBLY, MOUNTED ON THE FOAM PUMP INLET, IS A LOW PRESSURE
DEVICE. IT CANNOT WITHSTAND FLUSHING WATER PRESSURE. WHEN INSTALLING THE IN-LINE STRAINER
EQUIPPED WITH HALE MDT II OR MST, MAKE SURE THE IN-LINE STRAINER/VALVE ASSEMBLY IS IN THE HOSE
ON THE INLET SIDE OF THE VALVE. IF THE STRAINER IS SUBJECT TO FLUSHING WATER PRESSURE, USE
HALE FS SERIES STRAINERS.
The strainer/valve assembly has 1-
1/4” (32mm) NPT female threaded ports. Fittings are supplied for connection to the
following inside diameter hose, depending on the viscosity of foam concentrates used. (See Figure 3-
14: “In-Line
Strainer/Valve Installation,” on page 67.)
❑
3/4” (19mm)
❑
1.00” (25mm)
❑
1-
1/4” (32mm)
Use 3/4” (19mm) inside diameter hose for Class “A” foam and a 1.00” (25mm) inside diameter hose for Class “B” foams.
For high viscosity Class “B” foam concentrates use 1-1/4” (32mm) or 1-1/2” (38mm) inside diameter hose. (See Figure 23
In-Line Strainer/Valve Installation
). A bracket is included to permit installation on the apparatus.
Figure 23
: In-Line Strainer/Valve Installation
To Install the In-Line Strainer/Valve Assembly
1.
Choose a location on the apparatus that allows gravity feed from the foam tank to the strainer inlet
and
from the
strainer outlet to the foam pump suction connection.
Notes:
When selecting the strainer location, make sure there is sufficient space above and below the strainer.
❑
A minimum of 5” (127 mm) below for removal of the strainer basket and screen for cleaning
❑
2” (51 mm) above to permit operation of the service valve
2.
Mark 4 holes to mount the foam strainer bracket. Drill tapped holes for 1/4”-20 UNC screws (#7 drill for
¼-
20 UNC tap)...or...drill clearance holes for 9/32” (7 mm) for 1/4”-20 UNC screws. (See
Summary of Contents for SmartFOAM 1.7AHP
Page 3: ...Page 2 SmartFOAM NOTES...
Page 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Page 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Page 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Page 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Page 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Page 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM NOTES...
Page 80: ...79 Page 79 SmartFOAM NOTES...