Page
68
SmartFOAM
USER CALIBRATION
The complete Hale SmartFOAM
System’s foam pump
and motor assembly, controller unit and flow sensor is
tested at the factory before shipping to the installer. If the
Hale SmartFOAM system is properly installed, further
calibration IS NOT necessary until delivery to customer.
The system permits easy checking of component
calibration to assure accurate operation. The calibration
process verifies component calibration and allows
adjustments to the flow sensor and feedback sensor
display readings to allow for variations in apparatus
piping configurations and end user selected foam
concentrate.
Default values for simulated flow and foam concentrate
injection rate may be set to end user specifications while
in the calibration mode.
The SmartFOAM controller allows up to 6 user preset
foam injection rates. Each preset allows for custom text
and color for easy identification.
Note:
The Hale SmartFOAM system is calibrated at the
factory to U.S. measurement (GPM, PSI, GALLONS,
etc.) units. The system may be set to Metric units (see
heading
“English to Metric Units”). However, the same
unit of measurement must be used throughout the
calibration process to ensure proper proportioning by the
system.
Recalibration of the system may be required ONLY after
major repairs or component changes are made to the
Hale SmartFOAM foam system. Different viscosity foam
concentrates may also required recalibration.
ENTERING PASSWORDS
System calibration and configuration is accomplished by
accessing screens which are protected via passwords.
To enter a password:
1. Press the MENU button to go to the system
menu.
2. Press the Calibration/Configuration button on the
system menu screen.
3. Use the touch screen keypad to enter the
desired password.
a.
Press the “Enter” touch screen button to
submit the password.
b.
Press the “Delete last digit” touch screen
button to erase the last digit entered.
c.
Press the “Delete all digits” touch screen
button to erase all of the digits entered.
When a valid password is submitted the screen will
automatically change to the screen dictated by the password’s
value.
If an invalid password is submitted the display will show an “X”
across the password window for two seconds.
Figure 48
: Entering Passwords
WATER FLOW CALIBRATION
IMPORTANT!
AN ACCURATE FLOW MEASURING DEVICE MUST BE
USED TO MEASURE THE WATER FLOW WHEN
CALIBRATING THE FLOW SENSOR. USE A SUITABLE SIZE,
SMOOTH BORE, NOZZLE AND AN ACCURATE AND
CALIBRATED PITOT GAUGE INSTRUMENT. HAND HELD
PITOT GAUGES ARE USUALLY NOT VERY ACCURATE.
MAKE SURE THE SYSTEM IS CALIBRATED WITH AN
ACCURATE FLOW MEASURING DEVICE.
Summary of Contents for SmartFOAM 1.7AHP
Page 3: ...Page 2 SmartFOAM NOTES...
Page 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Page 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Page 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Page 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Page 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Page 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM NOTES...
Page 80: ...79 Page 79 SmartFOAM NOTES...