SmartFOAM
Upon initial power-up with the foam tanks empty, the
display on the controller unit will display a warning bar
indicating that the foam tank is low.
Figure 45
: Low Foam Tank Warning
1. Fill the foam concentrate tank with WATER. The
“
low foam tank” warning
indication clears from
the display indicating the low tank level sensor is
operating properly.
2. Place the bypass valve
’s handle to the
BYPASS
position to check the foam pump operation.
Place a calibrated five gallon container at the
discharge end of the bypass hose.
3. Place the system in simulated flow mode:
a. Press the MENU button.
b.
In the menu select the “simulated water
flow” button.
c. In the simulated water flow screen press
the ON/OFF button to toggle simulated
water flow. The icon indicates the
current state.
d. Set the simulated flow to 100 GPM by
using the INCR/DECR buttons.
e. Press the MENU button to return to the
menu.
f.
Press the RETURN button to return to
the operation screen.
Figure 46
: Setting Simulated Water Flow
Summary of Contents for SmartFOAM 1.7AHP
Page 3: ...Page 2 SmartFOAM NOTES...
Page 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Page 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Page 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Page 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Page 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Page 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM NOTES...
Page 80: ...79 Page 79 SmartFOAM NOTES...