ELECTRICAL CONNECTIONS
Complete harness electrical diagrams are provided - see
Figure 35
: SmartFOAM Harness Connections
. Refer
to these diagrams for proper installation of each of the
electrical components.
The Hale SmartFOAM system is designed to be installed
with a minimum of electrical connections. Cables are
provided with each Hale SmartFOAM system to make
the flow sensor, control unit and motor controller
connections.
The system installer must supply primary power wire,
low tank level sensor wire and flat braided ground
straps.
CAUTION!
Review the
“Safety” section of this manual in
its entirety before proceeding with electrical
connections.
❑
To prevent system damage or electrical shock the
main power supply wire must be the last connection
made to the Hale SmartFOAM motor controller.
❑
The cables provided with each Hale SmartFOAM
system contain shielded assemblies.
❑
NEVER attempt to shorten or lengthen the shielded
cables. If necessary order
❑
longer or shorter cables from Hale Products to suit
the particular installation.
❑
The cables are indexed so they connect to the
correct receptacle one way only. When making cable
connections DO NOT force mismatched connections
as damage can result, causing improper system
operation.
❑
The cables shipped with each Hale SmartFOAM are
tested at the factory with that unit. Improper handling
and forcing connections can damage these cables
which could result in other system damage.
❑
The system can only perform when the electrical
connections are sound. Make sure each electrical
connection is correct.
❑
Hale SmartFOAM systems are designed for use on
direct current, negative (
–) ground apparatus
electrical systems only.
❑
Do not mount radio transmitter or transmitter cables
in direct or close contact with the Hale SmartFOAM
unit.
❑
Before connecting the cables, inspect the O-ring
seal in the female connector. If the seal washer is
missing or damaged, water can enter the connector
causing corrosion of the pins and terminals resulting
in possible system failure.
❑
The ground strap must be a minimum of 1-
1/4”
(32mm) wide and no longer than
18” (457mm).
❑
A longer ground strap must be wider or a double
thickness strap must be used. Make sure the ground
strap is attached to the chassis frame. Grounding to
the body IS NOT acceptable.
❑
Always disconnect the power cable, ground straps,
electrical wires and cables from the control unit or
other Hale SmartFOAM equipment before electric
arc welding at any point on the apparatus. Failure to
do so could result in a power surge through the unit
that could cause irreparable damage.
❑
There are no user serviceable parts inside Hale
SmartFOAM system electrical/ electronic
components. Opening of these components
(distribution box or controller unit) voids the
warranty.
Summary of Contents for SmartFOAM 1.7AHP
Page 3: ...Page 2 SmartFOAM NOTES...
Page 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Page 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Page 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Page 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Page 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Page 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM NOTES...
Page 80: ...79 Page 79 SmartFOAM NOTES...