Page
63
SmartFOAM
SYSTEM INSTALLER START-UP
On initial power-up of the Hale SmartFOAM system at
the installer facility, the following procedures must be
followed.
INITIAL SYSTEM POWER CHECK
Watch the display on the controller unit as the apparatus
electrical system is turned ON. Check the controller unit
readout for:
❑
SmartFOAM booting screen is shown for three
seconds.
❑
SmartFOAM splash screen is shown for three
seconds.
❑
SmartFOAM version screen is shown for two
seconds.
❑
SmartFOAM preset screen is shown (default)
OR
SmartFOAM classic FoamLogix screen is
shown.
(The screen shown
depends on the “display
format” chosen in the user menu).
(See Figure 44
: Controller Unit Initialization
If a default display does not appear, refer to the
TROUBLESHOOTING section for possible WARM-UP/
SYSTEM CHECKING causes and solutions.
INITIAL SYSTEM CHECK
After initial system power-up the low tank level sensor
operation, foam pump operation, and flow sensor
calibration must be checked per the following:
CAUTION!
WATER IS USED AT THE SYSTEM INSTALLER
FACILITY TO VERIFY LOW TANK LEVEL SENSOR
SYSTEM READY OPERATION AND FOAM PUMP
OPERATION AS THE END USER SPECIFIED FOAM
CONCENTRATES MAY NOT BE READILY
AVAILABLE.
DO NOT PUMP WATER WITH THE HALE FOAM-
LOGIX FOAM PUMP FOR MORE THAN ONE (1)
MINUTE. DO NOT ATTEMPT TO CALIBRATE FOAM
PUMP FEEDBACK SENSOR WITH OTHER THAN
END USER SPECIFIED FOAM CONCENTRATE.
MAKE SURE THE BYPASS VALVE IS IN THE
BYPASS POSITION WHEN PUMPING WATER WITH
THE FOAM PUMP.
Figure 44
: Controller Unit Initialization
Summary of Contents for SmartFOAM 1.7AHP
Page 3: ...Page 2 SmartFOAM NOTES...
Page 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Page 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Page 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Page 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Page 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Page 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM NOTES...
Page 80: ...79 Page 79 SmartFOAM NOTES...