5.2 Nameplate for motor
The motor name plate is positioned on the motor
cooling fins.
The data and information on the motor nameplate
are described in the table below. See the nameplate
in fig.
on page
.
6. Mechanical installation
Before installing the pump, check that the pump type
and parts are as ordered.
6.1 Installation of pump
Install the pump on a plane surface using the
mounting holes in the motor base plate and a
minimum of four bolts. Tighten each of the four bolts
to a torque of 10 Nm.
Install the pump so that air locks are avoided in the
pump housing and pipework.
Figure
and the table below show the permissible
pump positions.
Fig. 1
Pump positions
●
Mounting in this position is allowed.
Install the pump so that inspection, maintenance and
service can easily be performed.
Install the pump in a well-ventilated location.
Pos. Description
1
Capacitor size and voltage
2
50 Hz motor efficiency at rated work point
3
50 Hz power factor
4
50 Hz output power in kW
5
Frequency
6
Number of phases
7
50 Hz output power in hp
8
50 Hz maximum current
9
50 Hz full-load current
10
50 Hz rated voltage
11
Motor type
12
50 Hz rated speed
13
Frequency
14
60 Hz output power in kW
15
NEMA enclosure class
16
60 Hz output power in hp
17
60 Hz power factor
18
60 Hz motor efficiency at rated work point
19
Part number
20
Factory code
21
Production date (year and week)
22
Country of origin
23
60 Hz rated voltage
24
60 Hz full-load current
25
60 Hz maximum current
26
60 Hz rated speed
27
IEC duty cycle
28
Number of poles
29
IEC enclosure class
30
Insulation class
31
NEMA enclosure type
32
Motor duty class
33
Maximum ambient temperature
34
NEMA locked-rotor code
35
NEMA design class
37
CC122B mark
38
CE mark
39
cURus mark
Warning
When pumping hot or cold liquids, make
sure that persons cannot accidentally
come into contact with hot or cold
surfaces.
TM
05 63
89 471
2
Pump
position
Non-self-priming
pumps
Self-priming
pumps
1
-
-
2
●
-
3
●
-
4
●
●
5
-
-
6
●
●
Up
Floor