GMV5 INDOOR UNIT SERVICE MANUAL
161
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
3. Remove the cover plate
component.
●Use a screwdriver to unscrew the
cover plate component.
4. Disassemble the
centrifugal fan.
●Use a screwdriver to unscrew the
centrifugal fan.
5. Remove the motor and
centrifugal fan.
●Use a screwdriver to unscrew the
centrifugal fan.
●Loosen the fasteners of the
motor and remove the motor from
the support.
●For motors that are accompanied
with supports, the supports need
removing as well.
6. Remove the centrifugal
fan.
●Use a hexagon to unscrew the
fan and remove the centrifugal fan
from the motor axle.
7. Install a new motor.
●Assemble units based on the
reverse order of this procedure
and power on the units for test.