2.2.2 Installation method
Fig.2.5 Installation of Wired Controller
Above is a simple installation method of wired controller. Please pay attention to the following:
Before installation, disconnect power of the indoor unit. Do not operate when power is connected.
Pull out the 2-core twisted pair cable from the installation hole on the wall and lead it through
the hole
on the back plate of wired controller.
Place the wired controller on wall and secure its back plate on wall with screw M4X25.
Connect the 2-core twisted pair cable to terminal H1 and terminal H2. Tighten up the screws.
Stick the cable in the slot that is
left of the terminals and buckle the wired controller’s panel with
its back plate.
Note:
If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord
according to above point 2 and point 5, strip some of the sheath of the communication cable to meet the
installation requirement.