GREE
GMV5 INDOOR UNIT SERVICE MANUAL
84
Setting Code
Setting Content
Setting Value
50: 50 seconds
60: 60 seconds
P42
Project number settings of
IDU
1-255
P43
Preferential operation
settings
00: no preferential operation
01: preferential operation
P44
One-key project number
setting query for IDU
00: not displayed
01: displayed
P45
One-key project number
reset for IDU
00: invalid
01: project number reset
P46
Accumulated time clearing
for air filter cleaning
00: not cleared
01: cleared
P47
Prompt settings for air filter
cleaning
00: no cleaning prompt settings
10-39: The first digit indicates the pollution degree of the using place
and the second digit indicates the accumulated operating time of
IDU. The two digits are described as follows:
Slight pollution: The first digit is
“1”. If the second digit is “0”, it
indicates that the accumulated operating time is 5500 hours. The
accumulated operating time is added by 500 hours when the second
digit is increased by
“1”. When the second digit is “9”, the
accumulated operating time is 10000 hours.
Medium pollution: The first digit is
“2”. If the second digit is “0”, it
indicates that the accumulated operating time is 1400 hours. The
accumulated operating time is added by 400 hours when the second
digit is increased by
“1”. When the second digit is “9”, the
accumulated operating time is 5000 hours.
Heavy pollution: The first digit is
“3”. If the second digit is “0”, it
indicates that the accumulated operating time is 100 hours. The
accumulated operating time is added by 100 hours when the second
digit is increased by
“1”. When the second digit is “9”, the
accumulated operating time is 1000 hours.
n0
System conservation
operation settings
00: comfortability preferred
01: conservation preferred
n1
Defrosting period settings
40: 40 minutes
50: 50 minutes
60: 60 minutes
n3
Forcible defrosting
00: no defrosting
01: forcible defrosting
A7
Silent function of ODU
00: no silent function
01-09: intelligent nighttime silent mode
10-12: forcible silent mode
n4
Highest capacity output
limitation settings
08: highest energy consumption limitation being 80%
09: highest energy consumption limitation being 90%
10: no conservation limitation
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...