GREE
GMV5 INDOOR UNIT SERVICE MANUAL
171
4.8 Floor Ceiling Type
Note:
The following steps are specific for GMV-ND140ZD/A-T units. For other units, the assembly and
disassembly procedure is similar except the numbers of centrifugal fans and motors.
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
1. Remove the air return
grille.
●Loosen the fasteners of the air
return grille and then remove the
grille.
2. Remove the left and right
cover plates.
●Use a screwdriver to unscrew the
left and right cover plates and then
remove the cover plates.
3. Remove the electric box
cover and the line
connecting to the motor.
●Use a screwdriver to unscrew the
electric box cover.
●Remove from the master board
the line connecting to the motor
and remove the tie.
4. Remove the limit board.
●Use a screwdriver to unscrew the
limit board and then remove the
board.
5. Remove the rear
connecting board.
●Use a screwdriver to unscrew the
rear connecting board and them
remove the board.
6. Remove the rear volute
casing.
●Loosen the fasteners that
connect the rear volute casing with
the front volute casing and remove
the rear volute casing.
7. Remove the front volute
casing.
●Use a screwdriver to unscrew the
front volute casing and then
remove the volute casing.
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...