Installation of the unit must be in accordance with National Electric Codes and local regulations.
Improper installation will affect unit’s performance, so do not install the unit by yourself. Please
contact local dealer to arrange professional technicians for the installation.
Do not connect power until all installation work is finished.
3.10.4 Selection of air switch and power cord
Model
Power Cord Size
Air Switch apacity
(A)
Minimum Sectional
Area of Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power Cord
(mm
2
/AWG)
GMV-ND22PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND25PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND28PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND32PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND36PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND40PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND45PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND50PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND56PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND63PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND72PL/B-T
220-240V~50Hz/208-
230V~60Hz
6
1.0/AWG18
1.0/AWG18
3.11 Installation of Air Handler type Indoor Unit
3.10.1 Outline and installation dimension
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...