GREE
GMV5 INDOOR UNIT SERVICE MANUAL
71
Parameter
Code
Parameter Name
Parameter Range
Default Value
Remark
P20
Environment
temperature
sensor settings
for IDU
01: temperature sensor
of air return vent
02: temperature sensor
of wired controller
03: temperature sensor
of air return vent for
cooling, dehumidifying,
and air supply;
temperature sensor of
wired controller for
heating
04: temperature sensor
of wired controller for
cooling, dehumidifying,
and air supply;
temperature sensor of
air return vent for
heating
03
When there are master and slave
wired controllers and the
temperature sensor of wired
controller is used, only the
temperature sensor of the master
wired controller is used by default.
Note:
1) In automatic mode, the
environment temperature sensor
settings are invalid for a common
IDU but the setting value is
memorized.
2)The environment temperature
sensor settings are invalid for a
fresh-air IDU. The temperature
sensor of air return vent is used by
default.
P21
Corrected value
of environment
temperature
sensor of IDU
(for cooling,
dehumidifying,
and air supply)
-15 to +15
Temperature
sensor of unit:
0°C; temperature
sensor of wired
controller: 0°C
Press
“ ” or “ ” to add or reduce
by 1°C.
P22
Corrected value
of environment
temperature
sensor of IDU
(for heating, fast
heating, and air
warming)
-15 to +15
Temperature
sensor of unit: -
2°C; temperature
sensor of wired
controller: 0°C
Press
“ ” or “ ” to add or reduce
by 1°C.
The temperature sensor of unit and
the temperature sensor of wired
controller share the same corrected
value.
In heating mode, corrected value of
temperature sensor of unit =
corrected value of temperature
sensor of wired controller - 2°C.
P32
Capacity
adjustment
function of IDU
-40% to +40%
00
Press
“ ” or “ ” to add or reduce
by 10%.
P35
Factory setting
recovery for user
functions
00: invalid
01: valid
00
Select
“01” and then press and
hold the
“ENTER/CANCEL” button
to restore the factory settings for
user functions (factory setting
recovery fails if remote shielding is
valid).
P36
Factory setting
recovery for
engineering
settings
00: invalid
01: valid
00
Select
“01” and then press and
hold the
“ENTER/CANCEL” button
to restore the factory status for
engineering settings (factory setting
recovery fails if remote shielding is
valid).
P40
Prevention for
heat collection
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
00
It indicates the number of seconds
for enabling the low-level fan every
15 minutes.
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...