GREE
GMV5 INDOOR UNIT SERVICE MANUAL
39
Model
GMV-
ND22G/A3A-
T
GMV-
ND28G/A3A-
T
GMV-
ND36G/A3A-
T
GMV-
ND45G/A3A-
T
GMV-
ND50G/A3A-
T
GMV-
ND56G/A3A-
T
*Minimum line current
A
0.1
0.1
0.15
0.15
0.15
0.2
*Maximum fuse current
A
6
6
6
6
6
6
Sound pressure level
dB(A)
38
38
44
44
44
44
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Piping
interface
Liquid pipe
mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ9.52
Gas pipe
mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ12.7
Φ15.9
Drain pipe
External diameter
×thickness
mm
Φ20×1.5
Φ20×1.5
Φ20×1.5
Φ20×1.5
Φ20×1.5
Φ30×1.5
Dimensions
W×D×H
mm
843×180
×275
843×180
×275
940×200
×298
940×200
×298
940×200
×298
1008×221
×319
Net weight
Main body
kg
10.0
10.0
12.5
12.5
12.5
15.0
Model
GMV-
ND63G/A3A-T
GMV-
ND71G/A3A-T
GMV-
ND80G/A3A-T
GMV-
ND90G/A3A-T
GMV-
ND100G/A3A-T
Horse Power
HP
3
3
4
4
4
Cooling capacity
kW
6.3
7.1
8.0
9.0
9.5
Heating capacity
kW
7.0
7.5
9.0
10.0
10.5
Air volume
m
3
/h
750
750
1550
1550
1650
Cooling power input
W
40
40
80
80
100
Cooling current input
A
0.17
0.17
0.41
0.41
0.41
Heating power input
W
40
40
80
80
100
Heating current input
A
0.17
0.17
0.41
0.41
0.41
*Minimum line current
A
0.2
0.2
0.2
0.2
0.2
*Maximum fuse current
A
6
6
6
6
6
Sound pressure level
dB(A)
44
44
49
49
52
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Piping
interface
Liquid pipe
mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Gas pipe
mm
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Drain pipe
External diameter
×thickness
mm
Φ30×1.5
Φ30×1.5
Φ30×1.5
Φ30×1.5
Φ30×1.5
Dimensions
W×D×H
mm 1008×221×319 1008×221×319 1350×258×326 1350×258×326 1350×258×326
Net weight
Main body
kg
15.0
15.0
18.5
18.5
18.5
Model
GMV-
ND22G/A8A-
T
GMV-
ND28G/A8A-
T
GMV-
ND36G/A8A-
T
GMV-
ND45G/A8A-
T
GMV-
ND50G/A8A-
T
GMV-
ND56G/A8A-
T
Horse Power
HP
1
1
1.5
2
2
2
Cooling capacity
kW
2.2
2.8
3.6
4.5
5.0
5.6
Heating capacity
kW
2.5
3.2
4.0
5.0
5.8
6.3
Air volume
m
3
/h
500
500
630
630
630
750
Cooling power input
W
20
20
30
30
30
40
Cooling current input
A
0.1
0.1
0.16
0.16
0.16
0.17
Heating power input
W
20
20
30
30
30
40
Heating current input
A
0.1
0.1
0.16
0.16
0.16
0.17
*Minimum line current
A
0.1
0.1
0.15
0.15
0.15
0.2
*Maximum fuse current
A
6
6
6
6
6
6
Sound pressure level
dB(A)
38
38
44
44
44
44
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...