GMV5 INDOOR UNIT SERVICE MANUAL
59
SN
Function Name
4
User parameter settings
5
Engineering parameter query
6
Engineering parameter settings
Engineering application functions can be operated through the IDU wired controller (XK46 or XK49
or XK79) or remote controller (YV1L1, fittings selectable).
5.1 Engineering Application Functions Operated through the
XK46 Wired Controller
5.1.1 Master IDU Settings
The master IDU can be set through the wired controller or remote controller. The methods for setting
the master IDU through the wired controller are as follows:
Method 1:
Step 1: Set an IDU to power-off status.
Step 2: Press and hold the
“MODE” button on the wired controller for more than five seconds.
Step 3: Check whether the setting is successful. If it is,
“MASTER” on the wired controller will be on.
Otherwise, repeat steps 1 and 2.
Method 2:
Step 1: Press and hold the
“FUNCTION” button for five seconds in power-on or power-off status to
enter the parameter query interface.
Step 2: Press and hold the
“FUNCTION” button for five seconds in “C00” status to enter the
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...