GREE
GMV5 INDOOR UNIT SERVICE MANUAL
95
Model
Power Cord Size
Air Switch apacity
(A)
Minimum Sectional
Area of Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power Cord
(mm
2
/AWG)
GMV-ND160PHS/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND224PH/A-T
220-240V/50Hz
208-230V/60Hz
10
1.0/AWG18
1.0/AWG18
GMV-ND280PH/A-T
220-240V/50Hz
208-230V/60Hz
16
1.0/AWG18
1.0/AWG18
3.3 Installation of Low Static Pressure Duct Type unit
3.3.1 Outline and installation dimension
Model: GMV-ND22PLS/A-T~GMV-ND63PLS/A-T.
Below are dimensions of A, B, C etc. for different models:
Unit:mm
Model
A
B
C
D
E
F
G
H
I
GMV-ND22PLS/A-T
742
491
700
615
200
121
528
161
580
GMV-ND25PLS/A-T
GMV-ND28PLS/A-T
GMV-ND32PLS/A-T
GMV-ND36PLS/A-T
GMV-ND40PLS/A-T
942
491
900
615
200
121
728
161
780
GMV-ND45PLS/A-T
GMV-ND50PLS/A-T
GMV-ND56PLS/A-T
1142
491
1100
615
200
121
928
161
980
GMV-ND63PLS/A-T
Summary of Contents for CM100N1320
Page 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Page 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Page 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Page 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Page 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Page 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Page 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Page 276: ...JF00302966...