RAW BRIDGE INPUT
Option
The
Raw Bridge Input
option lets you monitor the Wheatstone bridge
input signal (without offset correction) for troubleshooting purposes.
The acceptable range for this signal is -500 mV to +500 mV.
Note:
This signal also appears at test point E4 on the XMO2 printed
circuit board #703-1139.
The current
Raw Bridge Input
signal is displayed.
This completes the prompts for the
Raw Bridge Input
option, and the
XMO2 returns to the
Test Inputs?
menu.
OFFSET INPUT Option
The
Offset Input
option lets you monitor the XMO2 offset correction
signal. The acceptable range for this signal is 0 V to -4.000 V.
Note:
This signal also appears at test point E6 on the XMO2 printed
circuit board #703-1139.
The current
Offset Input
signal is displayed.
This completes the prompts for the
Offset Input
option, and the
XMO2 returns to the
Test Inputs?
menu.
TEST INPUTS
Press
[Y]
or
[Enter]
to view the
Raw Bridge input, or press
[N]
to
move to the next
Test Inputs?
option.
Raw Bridge Input?
Raw Bridge Input
When ready, press any key to
return to the
Test Inputs?
menu:
-x.x Bridge mV
TEST INPUTS
Press
[Y]
or
[Enter]
to view the
Offset input, or press
[N]
to move
to the next
Test Inputs?
option.
Offset Input?
Offset Input
When ready, press any key to
return to the
Test Inputs?
menu:
-x.xxx Offset V
Summary of Contents for XMO2
Page 8: ...Chapter 1 ...
Page 18: ...Chapter 2 ...
Page 30: ...Chapter 3 ...
Page 41: ...Chapter 4 ...
Page 52: ...Chapter 5 ...
Page 66: ...Chapter 6 ...
Page 114: ...Chapter 7 ...
Page 146: ...Chapter 8 ...
Page 159: ...Appendix A ...
Page 165: ...Appendix B ...
Page 177: ...Appendix C ...