September 2007
2-6
Installation
Cable Specifications
Table 2-2 below shows the transmitter wiring connections using the
standard GE XMO2 4-wire cable [P/N X4(L), where L = length in ft].
This cable can be used for distances up to 450 ft (137 m).
If you are using your own cable to wire the XMO2, refer to Table 2-3
below for cable requirements.
Table 2-4 below shows the connections for the GE standard 3-wire
RS232 cable (P/N 704-667, 668, 669, or 670-L, where L = length in
ft), which is available with a DB-9 or a DB-25 connector (male or
female). This cable is available in standard lengths of 6 ft and 12 ft.
See the
EIA-RS Serial Communications
booklet (GE document
#916-054) for a more detailed discussion of RS232 wiring.
Note:
See Figure B-4 on page B-4 for detailed drawings of the
standard GE cables described above.
Table 2-2: GE 4-Wire XMO2 Cable [P/N X4(L)]
Lead
Color
AWG
Terminal
+24 VDC Line
Red
22
TB1-1
–24 VDC Return
Black
22
TB1-2
4-20 mA (+)
White
22
TB1-3
4-20 mA (-)
Green
22
TB1-4
Table 2-3: Non-GE Cable Requirements
MAX. CABLE LENGTH
WIRE SIZE
ft
m
AWG
mm
2
450
130
22
0.35
700
200
20
0.60
1,050
320
18
1.00
1,700
500
16
1.20
2,800
850
14
2.00
4,000
1,200
12
3.00
Table 2-4: GE 3-Wire RS232 Cable (P/N 704-6xx-L)
Lead
Color
AWG
Terminal
RX
Red
22
TB1-6
TX
White
22
TB1-5
GND
Green
22
TB1-2
Summary of Contents for XMO2
Page 8: ...Chapter 1 ...
Page 18: ...Chapter 2 ...
Page 30: ...Chapter 3 ...
Page 41: ...Chapter 4 ...
Page 52: ...Chapter 5 ...
Page 66: ...Chapter 6 ...
Page 114: ...Chapter 7 ...
Page 146: ...Chapter 8 ...
Page 159: ...Appendix A ...
Page 165: ...Appendix B ...
Page 177: ...Appendix C ...