B-70
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F130
ENUMERATION: SIMULATION MODE
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F135
ENUMERATION: GAIN CALIBRATION
0 = 0x1, 1 = 1x16
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F138
ENUMERATION: OSCILLOGRAPHY FILE TYPE
0 = Data File, 1 = Configuration File, 2 = Header File
F140
ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE,
DISABLED
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V,
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A,
6 = Notched 2 A
F141
ENUMERATION: SELF TEST ERRORS
bitmask
error
0
Any Self Tests
1
Maintenance Alert
8
RRTD Communications Failure
10
FlexLogic Error Token
11
Equipment Mismatch
13
Unit Not Programmed
14
System Exception
15
Maintenance Alert
16
Ethernet Switch Failure
17
Maintenance Alert
18
Maintenance Alert
19
Maintenance Alert
20
Maintenance Alert
21
Maintenance Alert
22
Temperature Monitor
27
Remote Device Off
28
Direct Device Off
29
Maintenance Alert
30
Any Minor Error
31
Any Major Error
32
DSP Error
33
No DSP Interrupts
34
Unit Not Calibrated
35
EEPROM Data Error
36
SRAM Data Error
37
Program Memory
38
Watchdog Error
39
Low On Memory
40
Prototype Firmware
41
Module Failure 01
42
Module Failure 02
43
Module Failure 03
44
Module Failure 04
45
Module Failure 05
46
Module Failure 06
47
Module Failure 07
48
Module Failure 08
49
Module Failure 09
50
Incompatible H/W
52
Brick Trouble
53
Module Failure 10
54
Module Failure 11
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...