GE Multilin
L60 Line Phase Comparison System
5-239
5 SETTINGS
5.6 CONTROL ELEMENTS
5
5.6.11 AUTORECLOSE
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
AUTORECLOSE
Ö
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR MODE:
1 & 3 Pole
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
MESSAGE
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
MESSAGE
AR BLOCK BKR1:
Off
Range: FlexLogic™ operand
MESSAGE
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR BKR MAN CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
AR BLK TIME UPON MAN
CLS:
10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 1P INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3P INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3P TD INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR MULTI-P FAULT:
Off
Range: FlexLogic™ operand
MESSAGE
BKR ONE POLE OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 3 POLE OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 4:
4.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR EXTEND DEAD T 1:
Off
Range: FlexLogic™ operand
MESSAGE
AR DEAD TIME 1
EXTENSION: 0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR RESET:
Off
Range: FlexLogic™ operand
MESSAGE
AR RESET TIME:
60.00 s
Range: 0 to 655.35 s in steps of 0.01
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...