5-28
L60 Line Phase Comparison System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO1 STATUS CONFIGURATION
The
NUMBER OF STATUS POINTS IN GGIO1
setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the
NUMBER OF STATUS POINTS IN GGIO1
setting will not take effect until
the L60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO2 CONTROL...
Ö
GGIO2 CF SPSCO 1(64)
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L60
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO4 ANALOG CONFIGURATION
The
NUMBER OF ANALOG POINTS
setting determines how many analog data points will exist in GGIO4. When this value is
changed, the L60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
GGIO1 STATUS
CONFIGURATION
NUMBER OF STATUS
POINTS IN GGIO1: 8
Range: 8 to 128 in steps of 8
MESSAGE
GGIO1 INDICATION
1
Off
Range: FlexLogic™ operand
MESSAGE
GGIO1 INDICATION
2
Off
Range: FlexLogic™ operand
↓
MESSAGE
GGIO1 INDICATION 128
Off
Range: FlexLogic™ operand
GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 1
CTLMODEL: 1
Range: 0, 1, or 2
GGIO4 ANALOG
CONFIGURATION
NUMBER OF ANALOG
POINTS IN GGIO4:
8
Range: 4 to 32 in steps of 4
MESSAGE
GGIO4 ANALOG 1
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 2
MEASURED VALUE
↓
MESSAGE
GGIO4 ANALOG 32
MEASURED VALUE
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...