GE Multilin
L60 Line Phase Comparison System
B-15
APPENDIX B
B.4 MEMORY MAPPING
B
234C
Fault 1 Prefault Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
234E
Fault 1 Prefault Phase B Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
234F
Fault 1 Prefault Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2351
Fault 1 Prefault Phase C Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2352
Fault 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
2354
Fault 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
2355
Fault 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
2357
Fault 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
2358
Fault 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
235A
Fault 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
235B
Fault 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
235D
Fault 1 Phase A Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
235E
Fault 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2360
Fault 1 Phase B Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2361
Fault 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2363
Fault 1 Phase C Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2364
Fault 1 Type
0 to 11
---
1
F148
0 (NA)
2365
Fault 1 Location based on Line length units (km or miles)
-3276.7 to 3276.7
---
0.1
F002
0
2366
...Repeated for Fault 2
238C
...Repeated for Fault 3
23B2
...Repeated for Fault 4
23D8
...Repeated for Fault 5
Synchrocheck Actuals (Read Only) (2 modules)
2400
Synchrocheck 1 Delta Voltage
-1000000000000 to
1000000000000
V
1
F060
0
2402
Synchrocheck 1 Delta Frequency
0 to 655.35
Hz
0.01
F001
0
2403
Synchrocheck 1 Delta Phase
0 to 179.9
degrees
0.1
F001
0
2404
...Repeated for Synchrocheck 2
Autoreclose Status (Read Only) (6 modules)
2410
Autoreclose 1 Count
0 to 65535
---
1
F001
0
2411
Autoreclose 2 Count
0 to 65535
---
1
F001
0
2412
Autoreclose 3 Count
0 to 65535
---
1
F001
0
2413
Autoreclose 4 Count
0 to 65535
---
1
F001
0
2414
Autoreclose 5 Count
0 to 65535
---
1
F001
0
2415
Autoreclose 6 Count
0 to 65535
---
1
F001
0
Remote double-point status inputs (read/write setting registers and read only actaul value registers)
2608
Remote double-point status input 1 device
1 to 32
---
1
F001
1
2609
Remote double-point status input 1 item
0 to 128
---
1
F156
0 (None)
260A
Remote double-point status input 1 name
1 to 64
---
1
F205
"Rem Ip 1"
2610
Remote double-point status input 1 input state (read only)
0 to 3
---
1
F605
3 (Bad)
2611
Remote double-point status input 1 events
0 to 1
---
1
F102
0 (Disabled)
2612
... Repeated for double-point status input 2
---
---
---
---
---
261C
... Repeated for double-point status input 3
---
---
---
---
---
2626
... Repeated for double-point status input 4
---
---
---
---
---
2630
... Repeated for double-point status input 5
---
---
---
---
---
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
0 to 1
---
1
F108
0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00
Contact Input States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
2D80
Contact Output States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
2E00
Virtual Output States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (16 items)
0 to 1
---
1
F155
0 (Offline)
2F80
Remote Input States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...