GE Multilin
L60 Line Phase Comparison System
B-37
APPENDIX B
B.4 MEMORY MAPPING
B
730B
dcmA Inputs 1 Units
---
---
---
F206
“mA”
730E
dcmA Inputs 1 Range
0 to 6
---
1
F173
6 (4 to 20 mA)
730F
dcmA Inputs 1 Minimum Value
-9999.999 to 9999.999
---
0.001
F004
4000
7311
dcmA Inputs 1 Maximum Value
-9999.999 to 9999.999
---
0.001
F004
20000
7313
Reserved (5 items)
0 to 65535
---
1
F001
0
7318
...Repeated for dcmA Inputs 2
7330
...Repeated for dcmA Inputs 3
7348
...Repeated for dcmA Inputs 4
7360
...Repeated for dcmA Inputs 5
7378
...Repeated for dcmA Inputs 6
7390
...Repeated for dcmA Inputs 7
73A8
...Repeated for dcmA Inputs 8
73C0
...Repeated for dcmA Inputs 9
73D8
...Repeated for dcmA Inputs 10
73F0
...Repeated for dcmA Inputs 11
7408
...Repeated for dcmA Inputs 12
7420
...Repeated for dcmA Inputs 13
7438
...Repeated for dcmA Inputs 14
7450
...Repeated for dcmA Inputs 15
7468
...Repeated for dcmA Inputs 16
7480
...Repeated for dcmA Inputs 17
7498
...Repeated for dcmA Inputs 18
74B0
...Repeated for dcmA Inputs 19
74C8
...Repeated for dcmA Inputs 20
74E0
...Repeated for dcmA Inputs 21
74F8
...Repeated for dcmA Inputs 22
7510
...Repeated for dcmA Inputs 23
7528
...Repeated for dcmA Inputs 24
Disconnect switches (read/write settings)
7540
Disconnect switch 1 function
0 to 1
---
1
F102
0 (Disabled)
7541
Disconnect switch 1 name
---
---
---
F206
“SW 1"
7544
Disconnect switch 1 mode
0 to 1
---
1
F157
0 (3-Pole)
7545
Disconnect switch 1 open
0 to 65535
---
1
F300
0
7546
Disconnect switch 1 block open
0 to 65535
---
1
F300
0
7547
Disconnect switch 1 close
0 to 65535
---
1
F300
0
7548
Disconnect switch 1 block close
0 to 65535
---
1
F300
0
7549
Disconnect switch 1 phase A / three-pole closed
0 to 65535
---
1
F300
0
754A
Disconnect switch 1 phase A / three-pole opened
0 to 65535
---
1
F300
0
754B
Disconnect switch 1 phase B closed
0 to 65535
---
1
F300
0
754C
Disconnect switch 1 phase B opened
0 to 65535
---
1
F300
0
754D
Disconnect switch 1 phase C closed
0 to 65535
---
1
F300
0
754E
Disconnect switch 1 phase C opened
0 to 65535
---
1
F300
0
754F
Disconnect switch 1 operate time
0 to 2
s
0.001
F001
70
7550
Disconnect switch 1 alarm delay
0 to 1000000
s
0.001
F003
0
7552
Disconnect switch 1 events
0 to 1
---
1
F102
0 (Disabled)
7553
Reserved (2 items)
---
---
---
---
---
7555
...Repeated for disconnect switch 2
756A
...Repeated for disconnect switch 3
757F
...Repeated for disconnect switch 4
7594
...Repeated for disconnect switch 5
75A9
...Repeated for disconnect switch 6
75BE
...Repeated for disconnect switch 7
75D3
...Repeated for disconnect switch 8
75E8
...Repeated for disconnect switch 9
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...